View larger
EMD-SL-PH-400 2866077 PHOENIX CONTACT Monitoring relay
EMD-SL-PH-400
2866077
PHOENIX CONTACT
1 Pcs.
Automation > Phase monitoring relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for multi-phase electrical distribution protection, the Phoenix Contact EMD-SL-PH-400 monitoring relay continuously tracks system integrity to prevent equipment damage caused by irregular line conditions. This hardware integrates into switchgear enclosures to supervise phase presence and rotational order, safeguarding industrial loads from unexpected network faults.
Please note that specific pricing, availability, and lead times are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Phase sequence monitoring (EF003412): Yes
- Phase failure detection (EF003413): Yes
- Function under voltage detection (EF003414): No
- Function over voltage detection (EF003415): No
- Phase imbalance monitoring (EF003416): Yes
- Voltage measuring range (EF002486): 342 V
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Width (EF000008): 22.5 mm
- Height (EF000040): 90 mm
- Depth (EF000049): 113 mm
More info
▲Key Commercial Data
| Orderkey | 2866077 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 269 (C-5-2017) |
| GTIN | 4017918952679 |
| Weight per Piece (excluding packing) | 149.000 g |
| Custom tariff number | 85364900 |
| Country of origin | AT (Austria) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Input data
| Nominal input voltage UN | 400 V (3 N ~ 400/230 V) |
|---|---|
| Function | Phase sequence, phase failure, asymmetry |
| Min setting range of the voltage threshold value | 342 V AC |
| Max. setting range of the voltage threshold value | 457 V AC |
| Setting range for response delay | ≤ 350 ms (fixed setting) |
| Setting range for starting delay | ≤ 500 ms (fixed setting) |
| Asymmetry | Fixed, approx. 30 % |
| Recovery time | < 100 ms |
Contact side
| Contact type | 2 floating PDT contacts |
|---|---|
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
General
| Mechanical service life | approx. 2x 107cycles |
|---|---|
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Overvoltage category | III, basic insulation (as per EN 50178) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Color | green |
| Rated insulation voltage | 300 V (acc. to EN 50178) |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Connection data
| Conductor cross section flexible min. | 0.25 mm² |
|---|---|
| Conductor cross section flexible max. | 2.5 mm² |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Tightening torque | 1 Nm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-3 |
| Noise immunity | EN 61000-6-2 |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |