Phoenix Contact EMD-SL-PH-690 monitoring relay functions as a protective monitor for high-voltage three-phase industrial electrical networks. Industrial facilities rely on these devices to track phase failure and voltage thresholds, preventing electrical hazards and machine downtime. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Phase sequence monitoring (EF003412): Yes
- Phase failure detection (EF003413): Yes
- Function under voltage detection (EF003414): Yes
- Function over voltage detection (EF003415): No
- Phase imbalance monitoring (EF003416): No
- Voltage measuring range (EF002486): 177 V
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Width (EF000008): 22.5 mm
- Height (EF000040): 90 mm
- Depth (EF000049): 113 mm
More info
▲Key Commercial Data
| Orderkey | 2905597 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 269 (C-5-2017) |
| GTIN | 4046356967198 |
| Weight per Piece (excluding packing) | 156.400 g |
| Custom tariff number | 85364900 |
| Country of origin | AT (Austria) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 70 °C (C300) |
|---|---|
| -25 °C ... 55 °C (B300) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Input data
| Nominal input voltage UN | 690 V (3~ 208 V ... 690 V) |
|---|---|
| Input voltage range | 177 V ... 794 V (3~) |
| Function | Undervoltage, phase sequence, phase failure |
| Min setting range of the voltage threshold value | 177 V AC |
| Max. setting range of the voltage threshold value | 794 V AC |
| Setting range for response delay | 0.1 s ... 10 s |
| Basic accuracy | ≤ 3 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Asymmetry | 25 % |
| Recovery time | > 500 ms |
Contact side
| Contact type | 2 floating PDT contacts |
|---|---|
| Maximum switching voltage | 400 V AC |
| Interrupting rating (ohmic load) max. | 1250 VA (5 A/250 V AC at +55 °C) |
| 150 VA (5 A/30 V DC at +55°C) | |
| 75 VA (2.5 A/30 V DC at +70°C) | |
| Output fuse | 5 A (fast-blow) |
General
| Mechanical service life | 20x 106cycles |
|---|---|
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Overvoltage category | III (IEC 60664-1) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Color | green |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Connection data
| Conductor cross section flexible min. | 0.5 mm² |
|---|---|
| Conductor cross section flexible max. | 2.5 mm² |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.5 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Tightening torque | 1 Nm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
|---|---|
| Noise emission | EN 61326-1 |
| Noise immunity | EN 61326-1 |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |