PSI-REP-PROFIBUS/12MB 2708863 PHOENIX CONTACT Repeater
PSI-REP-PROFIBUS/12MB
2708863
PHOENIX CONTACT
1 Pcs.
Automation > PLC communication module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A PSI-REP-PROFIBUS/12MB 2708863 PHOENIX CONTACT Repeater is utilized within industrial networks to regenerate and extend communication signals across extended cable distances. Repeaters are commonly incorporated into expansive factory floor installations to maintain network integrity and prevent data packet degradation.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for TCP/IP (EF003050): No
- Supporting protocol for PROFIBUS (EF003052): Yes
- Supporting protocol for CAN (EF003053): No
- Supporting protocol for INTERBUS (EF003054): No
More info
▲Key Commercial Data
| Orderkey | 2708863 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 318 (C-6-2017) |
| GTIN | 4046356078993 |
| Weight per Piece (excluding packing) | 212.400 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 30 % ... 95 % (non-condensing) |
| Altitude | ≤ 5000 m (For restrictions see manufacturer's declaration) |
| ≤ 2000 m (When used in EX zone 2) | |
| Degree of protection | IP20 |
| Noise immunity | EN 61000-4-2 |
General
| Transmission channels | 2 (1/1), TD, RD, half duplex |
|---|---|
| Bit delay | 1 bit (Direct mode) |
| Bit distortion, input | max. ± 35 % |
| Bit distortion, output | < 6.25 % |
| Electrical isolation | VCC // TBUS // PROFIBUS (A) // PROFIBUS (B) |
| Test voltage data interfaces | 1.5 kV |
| Test voltage data interface/power supply | 1.5 kVrms(50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise emission | EN 55011 |
| Net weight | 212.4 g |
| Housing material | PA 6.6-FR |
| Color | green |
| MTBF | 1136 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 238 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| MTTF | 1638 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
| 812 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25 % (5 days a week, 12 hours a day)) | |
| 340 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) | |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC IIC T4 Gc X (Please follow the special installation instructions in the documentation!) |
| UL, USA/Canada | cULus listed UL 508 |
| Class I, Zone 2, AEx nA nC IIC T6 | |
| Class I, Zone 2, Ex nA nC IIC T6 Gc X | |
| Class I, Div. 2, Groups A, B, C, D |
Power supply
| Nominal supply voltage | 24 V DC (With UL approval) |
|---|---|
| Supply voltage range | 18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block) |
| Typical current consumption | < 90 mA (24 V DC) |
Serial interface
| Interface 1 | PROFIBUS acc. to IEC 61158, RS-485 2-conductor |
|---|---|
| Operating mode | Through PROFIBUS connector |
| Connection method | D-SUB-9 female connector |
| File format/coding | UART (11 Bit, NRZ) |
| Data direction switching | Automatic control, min. station response time 2 bits |
| Transmission medium | 2-wire twisted pair, shielded |
| Transmission length | ≤ 1200 m (Depends on transmission speed and cable type) |
| Termination resistor | external |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Output nominal voltage | 5 V DC ±5 % |
| Output current | 50 mA |
Digital outputs
| Output name | Relay output |
|---|---|
| Output description | Alarm output |
| Number of outputs | 1 |
| Maximum switching voltage | 30 V DC (1 A) |
| 65 V DC (0.46 A) | |
| 150 V AC (0.46 A) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Type of test | Free fall in acc. with IEC 60068-2-32 |
| Test result | 1 m |
| Type of test | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 |
| Test result | 5g, 10...150 Hz, 2.5 h, in XYZ direction |
| Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
| Test result | 15g, 11 ms period, half-sine shock pulse |
| Noise emission | EN 55011 |
| Noise immunity | EN 61000-4-2 |
| Free from substances that could impair the application of coating | according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 3 GHz |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-5 |
| Signal | ± 1 kV |
| Standards/regulations | EN 55011 |
| EN 61000-4-6 | |
| Designation | Air clearances and creepage distances |
| Standards/regulations | DIN EN 50178, DIN EN 60950 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC IIC T4 Gc X |
| UL, USA/Canada | cULus listed UL 508 |
| Class I, Zone 2, AEx nA nC IIC T6 | |
| Class I, Zone 2, Ex nA nC IIC T6 Gc X | |
| Class I, Div. 2, Groups A, B, C, D | |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |