PHOENIX CONTACT IB IL TEMP 4/8 RTD/EF-PAC IB IL TEMP 4/8 RTD/EF-PAC 2897402 PHOENIX CONTACT Inline terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

IB IL TEMP 4/8 RTD/EF-PAC 2897402 PHOENIX CONTACT Inline terminal

IB IL TEMP 4/8 RTD/EF-PAC

2897402

PHOENIX CONTACT

1 Pcs.

Inline terminal Inline, Temperature recording module, Analogue RTD inputs: 8 (for resistive temperature sensors), connection technology: 4 conductors, transmission rate on local bus: 500 kBit/s, protection rating: IP20, including inline connectors and marking fields

Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact Inline terminal interfaces resistive temperature detectors and resistance sensors with modular automation systems, delivering accurate thermal tracking for industrial processes. Terminal blocks of this type are routinely integrated into distributed control assemblies to monitor equipment operating temperatures.

Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage DC (EF007534): 19.2 V
  • Voltage type (supply voltage) (EF002991): DC
  • Input, current (EF003204): No
  • Input, voltage (EF003205): No
  • Input, resistor (EF003206): Yes
  • Input, resistance thermometer (EF003207): Yes
  • Input, thermocouple (EF003208): No
  • Input signal, configurable (EF003209): No
  • Resolution of the analogue inputs (EF003575): 24 Bit
  • Output, current (EF003212): No
  • Output, voltage (EF003213): No
  • Output signal configurable (EF003214): No
  • Number of analogue inputs (EF001994): 0
  • Number of analogue outputs (EF001995): 0
  • Analogue inputs configurable (EF008518): No
  • Analogue outputs configurable (EF008519): No

More info

▲

Key Commercial Data

Orderkey2897402
Packing unit1 pc
Catalog pagePage 165 (C-6-2017)
GTIN4046356288026
Weight per Piece (excluding packing)221.600 g
Custom tariff number85389091
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Dimensional drawing
Width48.8 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Mounting typeDIN rail
Net weight221.6 g
Note on weight specificationswith connectors
Operating modeProcess data mode with 5 words/1 word PCP
Diagnostics messagesFailure of the internal I/O supply I/O error message sent to the bus coupler
Failure of or insufficient communications power ULI/O error message sent to the bus coupler
User error Error message in the process data

Interfaces

DesignationInline local bus
No. of channels2
Connection methodInline data jumper
Transmission speed500 kbps
Transmission physicsCopper

Inline potentials

DesignationCommunications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current consumptiontyp. 95 mA
max. 120 mA
DesignationSupply of analog modules (UANA)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumptiontyp. 6 mA
max. 15 mA
Power consumptiontyp. 0.85 W (entire device)

Analog inputs

Number of inputs8 (for resistance temperature detectors)
Input nameAnalog RTD inputs
Description of the inputInput for resistive temperature sensors
Connection methodSpring-cage connection
Connection technology4-wire
Note regarding the connection technologyshielded
Sensor types (RTD) that can be usedPt, Ni, KTY, Cu sensors, linear resistors
Linear resistance measuring range0 Ω ... 500 Ω
0 Ω ... 5 kΩ
0 Ω ... 30 kΩ
Measuring principleSigma/Delta process
Measured value representation16 bits (15 bits + sign bit)
Resolution A/D24 bit
Process data update1.8 s (Up to 3.3 s possible depending on operating mode)
Data formatsIB IL, S7-compatible
Input filter time100 ms

Electrical isolation

Test section7.5 V supply (bus logic), 24 V supply UANA/ I/O 500 V AC 50 Hz 1 min.
7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min.
I/O / functional earth ground 500 V AC 50 Hz 1 min.

Standards and Regulations

Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.