Phoenix Contact PLC-APT-UI-IN is an extension module utilized in industrial control setups to expand input capabilities for various monitoring and measurement applications. These interface units bridge field instrumentation with the main controller, allowing accurate signal acquisition across complex automation networks.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of analogue inputs (EF001994): 1
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): Yes
- Analogue outputs configurable (EF008519): No
- Input, current (EF003204): Yes
- Input, voltage (EF003205): Yes
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): Yes
- Resolution of the analogue inputs (EF003575): 10 Bit
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Suitable for safety functions (EF001597): No
- Appendant operation agent (Ex ia) (EF004141): No
More info
▲Key Commercial Data
| Orderkey | 2906917 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 430 (C-5-2017) |
| GTIN | 4055626153780 |
| Weight per Piece (excluding packing) | 53.300 g |
| Custom tariff number | 85389099 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Supply
| Rated control circuit supply voltage US | 24 V DC |
|---|---|
| Rated control supply voltage range with reference to US | 0.8 ... 1.1 |
| Rated control supply current IS | 13 mA |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Operating voltage display | Green LED |
| Indication | Red LED |
Input data
| Input name | Analog current input |
|---|---|
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Input resistance current input | ~ 40 Ω |
| Maximum temperature coefficient | 0.01 %/K |
| Maximum transmission error | 1 % |
| Surge voltage protection | > 33 V |
| Input name | Analog voltage input |
| Voltage input signal | 0 V ... 10 V |
| 2 V ... 10 V | |
| Input resistance of voltage input | > 120 kΩ |
| Maximum temperature coefficient | 0.01 %/K |
| Maximum transmission error | 1 % |
| Surge voltage protection | > 33 V |
General
| Operating mode | 100% operating factor |
|---|---|
| Degree of protection | IP20 |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
| Number of connections | 4 |
Standards and Regulations
| Designation | Air clearances and creepage distances |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 50 V |
| Rated surge voltage | 0.5 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Conformance | CE-compliant |
| UL, USA/Canada | UL 508 Listed |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |