View larger
PLC-RSC- 24DC/21-21/EX 2909509 PHOENIX CONTACT Relay Module
PLC-RSC-24DC/21-21/EX
2909509
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A PLC-RSC- 24DC/21-21/EX 2909509 PHOENIX CONTACT Relay Module functions as an electromechanical switching interface designed to isolate control circuits from load circuits in industrial automation environments. This component routes signals securely between controllers and field devices while protecting sensitive electronics from voltage surges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage DC (EF003980): 20.2 V
- Voltage type for actuating (EF008242): DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.018 A
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2909509 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Catalog page | Page 458 (C-5-2017) |
| GTIN | 4055626363134 |
| Weight per Piece (excluding packing) | 70.630 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (UL) |
|---|---|
| -40 °C ... 60 °C (ATEX / IECEx) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 24 V DC |
|---|---|
| Typical input current at UN | 18 mA |
| Typical response time | 8 ms |
| Typical release time | 10 ms |
| Protective circuit | Reverse polarity protection Polarity protection diode |
| Free-wheeling diode Damping diode | |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 0.43 W |
Contact side
| Contact type | 2 PDT |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Minimum switching voltage | 5 V (at 10 mA) |
| Min. switching current | 10 mA (At 5 V) |
| Maximum inrush current | 15 A (300 ms) |
| Limiting continuous current | 6 A |
| Interrupting rating (ohmic load) max. | 140 W (at 24 V DC) |
| 85 W (at 48 V DC) | |
| 60 W (at 60 V DC) | |
| 44 W (at 110 V DC) | |
| 60 W (at 220 V DC) | |
| 1500 VA (for 250 V AC) | |
| Switching capacity | 2 A (at 24 V, DC13) |
| 0.2 A (at 250 V, DC13) | |
| 3 A (at 24 V, AC15) | |
| 3 A (at 120 V, AC15) | |
| 3 A (at 250 V, AC15) |
General
| Test voltage relay winding/relay contact | 4 kV AC (50 Hz, 1 min.) |
|---|---|
| Test voltage PDT/PDT | 2.5 kV AC (50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | RT III (Relay) |
| IP20 (Relay base) | |
| Mechanical service life | 3x 107cycles |
| ATEX | II 3G Ex ec nC IIC T4 Gc |
| EU-type examination certificate | IBExU16ATEXB015 X |
| IECEx | Ex ec nC IIC T4 Gc |
| IECEx certificate | IECEx IBE 16.0029X |
| UL, USA | Class I, Zone 2, AEx nA nC IIC T6 |
| UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D |
| UL, Canada | Class I, Zone 2, Ex nA nC IIC Gc T6 X |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 70.63 g |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1.5 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1.5 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| EN 60079-0, -7, -15 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV |
| Insulation | Safe isolation, reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant |
| ATEX | II 3G Ex ec nC IIC T4 Gc |
| IECEx | Ex ec nC IIC T4 Gc |
| UL, USA | Class I, Zone 2, AEx nA nC IIC T6 |
| UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D |
| UL, Canada | Class I, Zone 2, Ex nA nC IIC Gc T6 X |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |