PHOENIX CONTACT MINI MCR-EX-SD-23-38-LP-PT MINI MCR-EX-SD-23-38-LP-PT 1277114 PHOENIX CONTACT Ex i-Valve control block to activate solenoid valves with.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-EX-SD-23-38-LP-PT 1277114 PHOENIX CONTACT Ex i-Valve control block to activate solenoid valves with..

MINI MCR-EX-SD-23-38-LP-PT

1277114

PHOENIX CONTACT

1 Pcs.

Ex i-Valve control block to activate solenoid valves with intrinsic safety in the Ex zone. no-load voltage: 23 V DC, current limitation: 38 mA, Standard configuration, Loop-powered, Safety Integrity Level (SIL, IEC 61508): 3, Push-in connection Ex i, Valve control block for operating intrinsically safe solenoid valves in the zone Ex. No-load voltage: 23 V, current limiting: 38 mA, Loop-powered, Safety Integrity Level (SIL, IEC61508): 3, Push-in connection Ex i-Solenoid driver for controlling Ex i solenoid valves in the Ex area. no-load voltage: 23 V DC, current limitation: 38 mA, Standard configuration, Loop-powered, Safety Integrity Level (SIL, IEC 61508): 3, Push-in connection

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Designed for hazardous location safety implementations, this Phoenix Contact MINI MCR-EX-SD-23-38-LP-PT solenoid driver (part number 1277114) serves as an intrinsically safe valve control block. Industrial installations use such specialized driver modules to safely power and switch pneumatic or hydraulic control valves located in explosive atmospheres directly from safe-area PLC output cards.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Solenoid driver
  • Product family: MINI Analog Pro
  • Electrical isolation Overvoltage category: II (≤ 5000 m)
  • Pollution degree: 2 (≤ 5000 m)
  • Rated insulation voltage: 300 V rms
  • Test voltage: 2.5 kV AC (50 Hz, 60 s)
  • Insulation: Double/reinforced insulation
  • Rated insulation voltage: 265 V rms
  • Rated insulation voltage: 251 V rms
  • Supply Supply voltage range: loop-powered, no external supply necessary
  • Power consumption: < 1.5 W
  • Signal: Voltage Number of inputs: 1
  • Voltage input signal: 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
  • Signal: Voltage Number of outputs: 1
  • Output voltage: ≥ 12.5 V DC (38 mA)
  • Output resistor: ≥ 270 Ω (Internal resistance R i )

More info

▲
Technical data

Product properties
Product typeSolenoid driver
Product familyMINI Analog Pro

Electrical properties
Electrical isolation
Overvoltage categoryII (≤ 5000 m)
Pollution degree2 (≤ 5000 m)
Electrical isolation Input/output IEC/EN 61010-1
Standards/regulationsIEC/EN 61010-1
Rated insulation voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationDouble/reinforced insulation
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage265 Vrms
Electrical isolation Input/output IEC/EN 60079-7
Standards/regulationsIEC/EN 60079-7
Rated insulation voltage251 Vrms
Supply
Supply voltage rangeloop-powered, no external supply necessary
Power consumption< 1.5 W

Input data
Signal: Voltage
Number of inputs1
Voltage input signal19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)

Output data
Signal: Voltage
Number of outputs1
Output voltage≥ 12.5 V DC (38 mA)
Output resistor≥ 270 Ω (Internal resistance Ri)
Current limitation> 38 mA
Response time< 50 ms
Non-load voltage> 23 V DC
Short-circuit-proofyes

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12 (flexible)

Ex data
Ex installation (EPL)Gc
Div. 2
Ex i circuits (EPL)Ga
Da
Ma
Div. 1
Safety data
Max. internal inductance Linegligible
Max. internal capacitance Ci11 nF
Max. output voltage Uo27.1 V
Max. output current Io101 mA
Max. output power Po685 mW
Safety-related maximum voltage Um253 V AC
125 V DC
IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co23 mH / 2.3 µF
IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co12 mH / 686 nF
IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co3 mH / 78 nF
I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co30 mH / 4.1 µF

Dimensions
Width6.2 mm
Height109.81 mm
Depth119.2 mm

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Altitude range (IEC/EN 61010-1)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Rated insulation voltage300 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 61010-1)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Rated insulation voltage300 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 61010-1)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Rated insulation voltage150 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 60079-11)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Safety-related maximum voltage Um121 V AC
110 V DC
Rated insulation voltage150 Vrms(Input/output)
Altitude range (IEC/EN 60079-11)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Safety-related maximum voltage Um33 V AC/DC
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-11)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Safety-related maximum voltage Um33 V AC/DC
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Rated insulation voltage162 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Rated insulation voltage60 Vrms(Input/output)

Approvals
CE
CertificateCE-compliant
ATEX
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
CertificateTÜV 21 ATEX 8651 X
IECEx
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
CertificateIECEx TUR 21.0043 X
UKCA Ex (UKEX)
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
CertificateTÜV 21 UKEX 7021 X
CCC / China-Ex
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
Certificate2023122310116238
UL, USA/Canada
IdentificationUL 61010-2-201
Safety Integrity Level (SIL, IEC 61508)
Identification3

EMC data
Noise immunityIEC/EN 61000-6-2
IEC/EN 61326-3-2
Electromagnetic compatibilityTested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21
Noise emissionIEC/EN 61000-6-4

Standards and regulations
GB Standard
Standards/regulationsGB/T 3836.1
GB/T 3836.3
GB/T 3836.4

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.