View larger
MINI MCR-EX-SD-23-38-LP-PT 1277114 PHOENIX CONTACT Ex i-Valve control block to activate solenoid valves with..
MINI MCR-EX-SD-23-38-LP-PT
1277114
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for hazardous location safety implementations, this Phoenix Contact MINI MCR-EX-SD-23-38-LP-PT solenoid driver (part number 1277114) serves as an intrinsically safe valve control block. Industrial installations use such specialized driver modules to safely power and switch pneumatic or hydraulic control valves located in explosive atmospheres directly from safe-area PLC output cards.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Solenoid driver
- Product family: MINI Analog Pro
- Electrical isolation Overvoltage category: II (≤ 5000 m)
- Pollution degree: 2 (≤ 5000 m)
- Rated insulation voltage: 300 V rms
- Test voltage: 2.5 kV AC (50 Hz, 60 s)
- Insulation: Double/reinforced insulation
- Rated insulation voltage: 265 V rms
- Rated insulation voltage: 251 V rms
- Supply Supply voltage range: loop-powered, no external supply necessary
- Power consumption: < 1.5 W
- Signal: Voltage Number of inputs: 1
- Voltage input signal: 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
- Signal: Voltage Number of outputs: 1
- Output voltage: ≥ 12.5 V DC (38 mA)
- Output resistor: ≥ 270 Ω (Internal resistance R i )
More info
▲| Product type | Solenoid driver |
| Product family | MINI Analog Pro |
| Electrical isolation | |
| Overvoltage category | II (≤ 5000 m) |
| Pollution degree | 2 (≤ 5000 m) |
| Electrical isolation Input/output IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 300 Vrms |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Insulation | Double/reinforced insulation |
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 265 Vrms |
| Electrical isolation Input/output IEC/EN 60079-7 | |
| Standards/regulations | IEC/EN 60079-7 |
| Rated insulation voltage | 251 Vrms |
| Supply | |
| Supply voltage range | loop-powered, no external supply necessary |
| Power consumption | < 1.5 W |
| Signal: Voltage | |
| Number of inputs | 1 |
| Voltage input signal | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Signal: Voltage | |
| Number of outputs | 1 |
| Output voltage | ≥ 12.5 V DC (38 mA) |
| Output resistor | ≥ 270 Ω (Internal resistance Ri) |
| Current limitation | > 38 mA |
| Response time | < 50 ms |
| Non-load voltage | > 23 V DC |
| Short-circuit-proof | yes |
| Cross section AWG | (converted acc. to IEC) |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² (with ferrule) |
| 0.14 mm² ... 2.5 mm² (without ferrule) | |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 (flexible) |
| Ex installation (EPL) | Gc |
| Div. 2 | |
| Ex i circuits (EPL) | Ga |
| Da | |
| Ma | |
| Div. 1 | |
| Safety data | |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | 11 nF |
| Max. output voltage Uo | 27.1 V |
| Max. output current Io | 101 mA |
| Max. output power Po | 685 mW |
| Safety-related maximum voltage Um | 253 V AC |
| 125 V DC | |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 23 mH / 2.3 µF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 12 mH / 686 nF |
| IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 3 mH / 78 nF |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 30 mH / 4.1 µF |
| Width | 6.2 mm |
| Height | 109.81 mm |
| Depth | 119.2 mm |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Altitude range (IEC/EN 61010-1) | |
| Height range | > 2000 m ... 3000 m |
| Ambient temperature (operation) | -40 °C ... 63 °C |
| Rated insulation voltage | 300 Vrms(Input/output) |
| Insulation | Double/reinforced insulation |
| Altitude range (IEC/EN 61010-1) | |
| Height range | > 3000 m ... 4000 m |
| Ambient temperature (operation) | -40 °C ... 56 °C |
| Rated insulation voltage | 300 Vrms(Input/output) |
| Insulation | Double/reinforced insulation |
| Altitude range (IEC/EN 61010-1) | |
| Height range | > 4000 m ... 5000 m |
| Ambient temperature (operation) | -40 °C ... 49 °C |
| Rated insulation voltage | 150 Vrms(Input/output) |
| Insulation | Double/reinforced insulation |
| Altitude range (IEC/EN 60079-11) | |
| Height range | > 2000 m ... 3000 m |
| Ambient temperature (operation) | -40 °C ... 63 °C |
| Safety-related maximum voltage Um | 121 V AC |
| 110 V DC | |
| Rated insulation voltage | 150 Vrms(Input/output) |
| Altitude range (IEC/EN 60079-11) | |
| Height range | > 3000 m ... 4000 m |
| Ambient temperature (operation) | -40 °C ... 56 °C |
| Safety-related maximum voltage Um | 33 V AC/DC |
| Rated insulation voltage | 60 Vrms(Input/output) |
| Altitude range (IEC/EN 60079-11) | |
| Height range | > 4000 m ... 5000 m |
| Ambient temperature (operation) | -40 °C ... 49 °C |
| Safety-related maximum voltage Um | 33 V AC/DC |
| Rated insulation voltage | 60 Vrms(Input/output) |
| Altitude range (IEC/EN 60079-7) | |
| Height range | > 2000 m ... 3000 m |
| Ambient temperature (operation) | -40 °C ... 63 °C |
| Rated insulation voltage | 162 Vrms(Input/output) |
| Altitude range (IEC/EN 60079-7) | |
| Height range | > 3000 m ... 4000 m |
| Ambient temperature (operation) | -40 °C ... 56 °C |
| Rated insulation voltage | 60 Vrms(Input/output) |
| Altitude range (IEC/EN 60079-7) | |
| Height range | > 4000 m ... 5000 m |
| Ambient temperature (operation) | -40 °C ... 49 °C |
| Rated insulation voltage | 60 Vrms(Input/output) |
| CE | |
| Certificate | CE-compliant |
| ATEX | |
| Identification | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1) G Ex ec [ia Ga] IIC T4 Gc | |
| I (M1) [Ex ia Ma] I | |
| Certificate | TÜV 21 ATEX 8651 X |
| IECEx | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Certificate | IECEx TUR 21.0043 X |
| UKCA Ex (UKEX) | |
| Identification | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1) G Ex ec [ia Ga] IIC T4 Gc | |
| I (M1) [Ex ia Ma] I | |
| Certificate | TÜV 21 UKEX 7021 X |
| CCC / China-Ex | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| Certificate | 2023122310116238 |
| UL, USA/Canada | |
| Identification | UL 61010-2-201 |
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 3 |
| Noise immunity | IEC/EN 61000-6-2 |
| IEC/EN 61326-3-2 | |
| Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 |
| Noise emission | IEC/EN 61000-6-4 |
| GB Standard | |
| Standards/regulations | GB/T 3836.1 |
| GB/T 3836.3 | |
| GB/T 3836.4 | |