PHOENIX CONTACT MINI MCR-EX-SD-23-38-LP MINI MCR-EX-SD-23-38-LP 1277111 PHOENIX CONTACT Ex i-Valve control block to activate solenoid valves with in.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-EX-SD-23-38-LP 1277111 PHOENIX CONTACT Ex i-Valve control block to activate solenoid valves with in..

MINI MCR-EX-SD-23-38-LP

1277111

PHOENIX CONTACT

1 Pcs.

Ex i-Valve control block to activate solenoid valves with intrinsic safety in the Ex zone. no-load voltage: 23 V DC, current limitation: 38 mA, Standard configuration, Loop-powered, Safety Integrity Level (SIL, IEC 61508): 3, Screw connection Ex i, Valve control block for operating intrinsically safe solenoid valves in the Ex. zone No-load voltage: 23 V, current limiting: 38 mA, Loop-powered, Safety Integrity Level (SIL, IEC61508): 3, Screw connection Ex i-Solenoid driver for controlling Ex i solenoid valves in the Ex area. no-load voltage: 23 V DC, current limitation: 38 mA, Standard configuration, Loop-powered, Safety Integrity Level (SIL, IEC 61508): 3, Screw connection

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact MINI MCR-EX-SD-23-38-LP Ex i-valve control block activates intrinsically safe solenoid valves and field actuators in explosive environments. These compact interface modules provide loop-powered operation and secure isolation to protect automated systems.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Solenoid driver
  • Product family: MINI Analog Pro
  • Electrical isolation Overvoltage category: II (≤ 5000 m)
  • Pollution degree: 2 (≤ 5000 m)
  • Rated insulation voltage: 300 V rms
  • Test voltage: 2.5 kV AC (50 Hz, 60 s)
  • Insulation: Double/reinforced insulation
  • Rated insulation voltage: 265 V rms
  • Rated insulation voltage: 251 V rms
  • Supply Supply voltage range: loop-powered, no external supply necessary
  • Power consumption: < 1.5 W
  • Signal: Voltage Number of inputs: 1
  • Voltage input signal: 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
  • Signal: Voltage Number of outputs: 1
  • Output voltage: ≥ 12.5 V DC (38 mA)
  • Output resistor: ≥ 270 Ω (Internal resistance R i )

More info

▲
Technical data

Product properties
Product typeSolenoid driver
Product familyMINI Analog Pro

Electrical properties
Electrical isolation
Overvoltage categoryII (≤ 5000 m)
Pollution degree2 (≤ 5000 m)
Electrical isolation Input/output IEC/EN 61010-1
Standards/regulationsIEC/EN 61010-1
Rated insulation voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationDouble/reinforced insulation
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage265 Vrms
Electrical isolation Input/output IEC/EN 60079-7
Standards/regulationsIEC/EN 60079-7
Rated insulation voltage251 Vrms
Supply
Supply voltage rangeloop-powered, no external supply necessary
Power consumption< 1.5 W

Input data
Signal: Voltage
Number of inputs1
Voltage input signal19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)

Output data
Signal: Voltage
Number of outputs1
Output voltage≥ 12.5 V DC (38 mA)
Output resistor≥ 270 Ω (Internal resistance Ri)
Current limitation> 38 mA
Response time< 50 ms
Non-load voltage> 23 V DC
Short-circuit-proofyes

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodScrew connection
Stripping length10 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 1.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12 (flexible)
Tightening torque0.5 Nm ... 0.6 Nm

Ex data
Ex installation (EPL)Gc
Div. 2
Ex i circuits (EPL)Ga
Da
Ma
Div. 1
Safety data
Max. internal inductance Linegligible
Max. internal capacitance Ci11 nF
Max. output voltage Uo27.1 V
Max. output current Io101 mA
Max. output power Po685 mW
Safety-related maximum voltage Um253 V AC
125 V DC
IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co23 mH / 2.3 µF
IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co12 mH / 686 nF
IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co3 mH / 78 nF
I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co30 mH / 4.1 µF

Dimensions
Width6.2 mm
Height109.81 mm
Depth119.2 mm

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Altitude range (IEC/EN 61010-1)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Rated insulation voltage300 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 61010-1)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Rated insulation voltage300 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 61010-1)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Rated insulation voltage150 Vrms(Input/output)
InsulationDouble/reinforced insulation
Altitude range (IEC/EN 60079-11)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Safety-related maximum voltage Um121 V AC
110 V DC
Rated insulation voltage150 Vrms(Input/output)
Altitude range (IEC/EN 60079-11)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Safety-related maximum voltage Um33 V AC/DC
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-11)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Safety-related maximum voltage Um33 V AC/DC
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 2000 m ... 3000 m
Ambient temperature (operation)-40 °C ... 63 °C
Rated insulation voltage162 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 3000 m ... 4000 m
Ambient temperature (operation)-40 °C ... 56 °C
Rated insulation voltage60 Vrms(Input/output)
Altitude range (IEC/EN 60079-7)
Height range> 4000 m ... 5000 m
Ambient temperature (operation)-40 °C ... 49 °C
Rated insulation voltage60 Vrms(Input/output)

Approvals
CE
CertificateCE-compliant
ATEX
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
CertificateTÜV 21 ATEX 8651 X
IECEx
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Ma] I
CertificateIECEx TUR 21.0043 X
UKCA Ex (UKEX)
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
CertificateTÜV 21 UKEX 7021 X
CCC / China-Ex
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex ec [ia Ga] IIC T4 Gc
Certificate2023122310116238
UL, USA/Canada
IdentificationUL 61010-2-201
Safety Integrity Level (SIL, IEC 61508)
Identification3

EMC data
Noise immunityIEC/EN 61000-6-2
IEC/EN 61326-3-2
Electromagnetic compatibilityTested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21
Noise emissionIEC/EN 61000-6-4

Standards and regulations
GB Standard
Standards/regulationsGB/T 3836.1
GB/T 3836.3
GB/T 3836.4

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.