View larger
MINI MCR-2-V8-MOD-TCP 2905635 PHOENIX CONTACT Communication module
MINI MCR-2-V8-MOD-TCP
2905635
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MINI MCR-2-V8-MOD-TCP 2905635 PHOENIX CONTACT Communication module bridges disparate industrial networks, allowing field instruments and signal conditioners to transmit operational data to supervisory control systems. These modules ensure reliable data exchange across automation protocols in complex plant environments.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for EtherNet/IP (EF007521): No
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- IO link master (EF007298): No
- System accessory (EF004118): Yes
- Degree of protection (IP) (EF005474): IP20
- With potential separation (EF003272): No
- Suitable for rail mounting (EF003972): No
- Wall mounting/direct mounting (EF007020): No
- Front built-in possible (EF007016): No
- Rack-assembly possible (EF007018): No
- Suitable for safety functions (EF001597): No
- Appendant operation agent (Ex ia) (EF004141): No
- Appendant operation agent (Ex ib) (EF004142): No
More info
▲Key Commercial Data
| Orderkey | 2905635 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 96 (C-5-2017) |
| GTIN | 4046356996716 |
| Weight per Piece (excluding packing) | 205.100 g |
| Custom tariff number | 85389099 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Supply
| Nominal supply voltage range | 12 V ... 24 V |
|---|---|
| Supply voltage range | 9.6 V ... 30 V |
| Typical current consumption | 130 mA (at 9.6 V DC) |
| Power consumption | < 1200 mW |
Input data
| Available input sources | floating switch contact |
|---|---|
| Current source | |
| Number of inputs | 8 |
| Configurable/programmable | Yes |
| Current input signal | 4 mA ... 20 mA |
| Maximum input current | 24 mA |
| Input resistance current input | 50 Ω |
| Maximum input voltage | 5 V |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Transmission speed | 10 Mbps |
| 100 Mbps | |
| Data update rate | 15 ms |
General
| Maximum transmission error | 0.1 % |
|---|---|
| Maximum temperature coefficient | 0.01 % |
| Degree of protection | IP20 (Finger safety) |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 50 Vrms |
| Test voltage, input/output/supply | 0.5 kV |
| Status display | Green LED |
| Indication | Red LED |
| Housing material | PBT 7% GF V0 |
| Mounting position | any |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Permissible humidity (storage/transport) | 5 % ... 95 % |
| Maximum altitude | 4000 m |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Conformance | CE-compliant |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| Class I, Zone 2, Group IIC T5 | |
| GL | GL applied for |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |