View larger
MINI MCR-2-UI-I-OLP 2902061 PHOENIX CONTACT Loop-powered isolators
MINI MCR-2-UI-I-OLP
2902061
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MINI MCR-2-UI-I-OLP loop-powered isolators provide galvanic isolation and signal conversion in industrial measurement chains without requiring an auxiliary power supply. These devices protect sensitive control hardware by breaking ground loops and filtering electrical noise present in analog signal wiring. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 8 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 1
- Number of input ranges -100 mV ... +100 mV (EF006912): 1
- Number of input ranges -300 mV ... +300 mV (EF006920): 1
- Number of input ranges -500 mV ... +500 mV (EF006926): 1
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 1
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 1
- Number of input ranges -5 V ... +5 V (EF006923): 1
- Number of input ranges -10 V ... +10 V (EF006909): 1
- Number of input ranges -20 V ... +20 V (EF006917): 1
- Number of input ranges 0 mV ... 60 mV (EF006905): 1
- Number of input ranges 0 mV ... 100 mV (EF006893): 1
- Number of input ranges 0 mV ... 200 mV (EF006898): 1
- Number of input ranges 0 mV ... 300 mV (EF006901): 1
- Number of input ranges 0 mV ... 500 mV (EF006904): 1
More info
▲Key Commercial Data
| Orderkey | 2902061 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 79 (C-5-2017) |
| GTIN | 4046356652100 |
| Weight per Piece (excluding packing) | 107.900 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Input data
| Number of inputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Voltage input signal | 0 mV ... 1000 mV |
| 0 mV ... 750 mV | |
| 0 mV ... 500 mV | |
| 0 mV ... 300 mV | |
| 0 mV ... 250 mV | |
| 0 mV ... 200 mV | |
| 0 mV ... 125 mV | |
| 0 mV ... 120 mV | |
| 0 mV ... 150 mV | |
| 0 mV ... 100 mV | |
| 0 mV ... 75 mV | |
| 0 mV ... 60 mV | |
| 0 mV ... 50 mV | |
| 0 V ... 10 V | |
| 0 V ... 7.5 V | |
| 0 V ... 5 V | |
| 0 V ... 3 V | |
| 0 V ... 2.5 V | |
| 0 V ... 2 V | |
| 0 V ... 1.5 V | |
| 0 V ... 1.25 V | |
| 0 V ... 1.2 V | |
| 0 V ... 30 V | |
| 0 V ... 25 V | |
| 0 V ... 20 V | |
| 0 V ... 12.5 V | |
| 0 V ... 12 V | |
| 0 V ... 15 V | |
| -1000 mV ... 1000 mV | |
| -750 mV ... 750 mV | |
| -500 mV ... 500 mV | |
| -300 mV ... 300 mV | |
| -250 mV ... 250 mV | |
| -200 mV ... 200 mV | |
| -125 mV ... 125 mV | |
| -120 mV ... 120 mV | |
| -150 mV ... 150 mV | |
| -100 mV ... 100 mV | |
| -75 mV ... 75 mV | |
| -60 mV ... 60 mV | |
| -50 mV ... 50 mV | |
| -10 V ... 10 V | |
| -7.5 V ... 7.5 V | |
| -5 V ... 5 V | |
| -3 V ... 3 V | |
| -2.5 V ... 2.5 V | |
| -2 V ... 2 V | |
| -1.25 V ... 1.25 V | |
| -1.2 V ... 1.2 V | |
| -1.5 V ... 1.5 V | |
| -30 V ... 30 V | |
| -25 V ... 25 V | |
| -20 V ... 20 V | |
| -12.5 V ... 12.5 V | |
| -12 V ... 12 V | |
| additional areas can be configured, see table | |
| 1 V ... 5 V | |
| 1 V ... 5 V | |
| Current input signal | 0 mA ... 40 mA |
| 0 mA ... 30 mA | |
| 0 mA ... 20 mA | |
| 0 mA ... 12 mA | |
| 0 mA ... 10 mA | |
| 0 mA ... 8 mA | |
| 0 mA ... 7.5 mA | |
| 0 mA ... 5 mA | |
| 0 mA ... 6 mA | |
| 0 mA ... 4 mA | |
| 0 mA ... 3 mA | |
| 0 mA ... 2.5 mA | |
| 0 mA ... 2 mA | |
| 4 mA ... 20 mA | |
| 2 mA ... 10 mA | |
| 1 mA ... 5 mA | |
| max. input voltage | < 30 V |
| Max. input current | 50 mA (Dielectric strength up to 30 V) |
| Input resistance of voltage input | approx. 100 kΩ (At ≤ 1 V, otherwise approximately 1 MΩ) |
| Input resistance current input | 25 Ω (+ 0.7 V for test diode) |
Output data
| Number of outputs | 1 |
|---|---|
| Current output signal | 4 mA ... 20 mA |
| Max. output current | 32 mA |
| Load/output load current output | < 1000 Ω ((UB- 8 V) / 22 mA) |
| Ripple | < 10 mVrms(at 600 Ω) |
Power supply
| Supply voltage range | 8 V DC ... 30 V DC (no separate supply voltage necessary) |
|---|---|
| Typical current consumption | ≤ 20 mA |
| Power consumption | ≤ 600 mW |
Connection data
| Connection method | Screw connection |
|---|---|
| Single conductor/terminal point, solid, with ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, with ferrule, max. | 1.5 mm² |
| Single conductor/terminal point, solid, without ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, without ferrule, max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Min. AWG conductor cross section, flexible | 24 |
| Max. AWG conductor cross section, flexible | 12 |
| Stripping length | 10 mm |
| Screw thread | M3 |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | ≤ 0.1 % (of final value) |
| Maximum temperature coefficient | 0.01 %/K |
| Temperature coefficient, typical | 0.005 %/K |
| Limit frequency (3 dB) | approx. 30 Hz |
| Step response (10-90%) | 20 ms |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V (effective) |
| Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | gray |
| Housing material | PBT |
| Mounting position | any |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| Class I, Zone 2, Group IIC T5 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| Class I, Zone 2, Group IIC T5 | |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |