View larger
MINI MCR-2-U-UI 2902019 PHOENIX CONTACT 3-way signal conditioner, with configurable input/output, for electr..
MINI MCR-2-U-UI
2902019
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Configurable for diverse automation tasks, the Phoenix Contact MINI MCR-2-U-UI is a 3-way signal conditioner with flexible input and output options designed for electrical installation needs. Signal conditioners isolate, filter, and convert electrical signals to eliminate noise and ensure accurate data transmission across complex control networks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 9.6 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 1
- Number of input ranges -100 mV ... +100 mV (EF006912): 1
- Number of input ranges -300 mV ... +300 mV (EF006920): 1
- Number of input ranges -500 mV ... +500 mV (EF006926): 1
- Number of input ranges -1 V ... +1 V (EF006906): 1
- Number of input ranges -2 V ... +2 V (EF006913): 1
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 1
- Number of input ranges -10 V ... +10 V (EF006909): 1
- Number of input ranges -20 V ... +20 V (EF006917): 1
- Number of input ranges 0 mV ... 60 mV (EF006905): 1
- Number of input ranges 0 mV ... 100 mV (EF006893): 1
- Number of input ranges 0 mV ... 200 mV (EF006898): 1
- Number of input ranges 0 mV ... 300 mV (EF006901): 1
- Number of input ranges 0 mV ... 500 mV (EF006904): 1
More info
▲Key Commercial Data
| Orderkey | 2902019 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 74 (C-5-2019) |
| GTIN | 4046356649674 |
| Weight per Piece (excluding packing) | 140.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Degree of protection | IP20 (not assessed by UL) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
| Number of inputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Voltage input signal | -50 mV ... 50 mV (via DIP switch) |
| 0 mV ... 50 mV (via DIP switch) | |
| -60 mV ... 60 mV (via DIP switch) | |
| 0 mV ... 60 mV (via DIP switch) | |
| -75 mV ... 75 mV (via DIP switch) | |
| 0 mV ... 75 mV (via DIP switch) | |
| -80 mV ... 80 mV (via DIP switch) | |
| 0 mV ... 80 mV (via DIP switch) | |
| -100 mV ... 100 mV (via DIP switch) | |
| 0 mV ... 100 mV (via DIP switch) | |
| -120 mV ... 120 mV (via DIP switch) | |
| 0 mV ... 120 mV (via DIP switch) | |
| -150 mV ... 150 mV (via DIP switch) | |
| 0 mV ... 150 mV (via DIP switch) | |
| -200 mV ... 200 mV (via DIP switch) | |
| 0 mV ... 200 mV (via DIP switch) | |
| -240 mV ... 240 mV (via DIP switch) | |
| 0 mV ... 240 mV (via DIP switch) | |
| -300 mV ... 300 mV (via DIP switch) | |
| 0 mV ... 300 mV (via DIP switch) | |
| -500 mV ... 500 mV (via DIP switch) | |
| 0 mV ... 500 mV (via DIP switch) | |
| -600 mV ... 600 mV (via DIP switch) | |
| 0 mV ... 600 mV (via DIP switch) | |
| -750 mV ... 750 mV (via DIP switch) | |
| 0 mV ... 750 mV (via DIP switch) | |
| -800 mV ... 800 mV (via DIP switch) | |
| 0 mV ... 800 mV (via DIP switch) | |
| -1 V ... 1 V (via DIP switch) | |
| 0 V ... 1 V (via DIP switch) | |
| -1.2 V ... 1.2 V (via DIP switch) | |
| 0 V ... 1.2 V (via DIP switch) | |
| -1.5 V ... 1.5 V (via DIP switch) | |
| 0 V ... 1.5 V (via DIP switch) | |
| -2 V ... 2 V (via DIP switch) | |
| 0 V ... 2 V (via DIP switch) | |
| -2.4 V ... 2.4 V (via DIP switch) | |
| 0 V ... 2.4 V (via DIP switch) | |
| -3 V ... 3 V (via DIP switch) | |
| 0 V ... 3 V (via DIP switch) | |
| -5 V ... 5 V (via DIP switch) | |
| 0 V ... 5 V (via DIP switch) | |
| -6 V ... 6 V (via DIP switch) | |
| 0 V ... 6 V (via DIP switch) | |
| -7.5 V ... 7.5 V (via DIP switch) | |
| 0 V ... 7.5 V (via DIP switch) | |
| -8 V ... 8 V (via DIP switch) | |
| 0 V ... 8 V (via DIP switch) | |
| -10 V ... 10 V (via DIP switch) | |
| 0 V ... 10 V (via DIP switch) | |
| -12 V ... 12 V (via DIP switch) | |
| 0 V ... 12 V (via DIP switch) | |
| -15 V ... 15 V (via DIP switch) | |
| 0 V ... 15 V (via DIP switch) | |
| -20 V ... 20 V (via DIP switch) | |
| 0 V ... 20 V (via DIP switch) | |
| -24 V ... 24 V (via DIP switch) | |
| 0 V ... 24 V (via DIP switch) | |
| -30 V ... 30 V (via DIP switch) | |
| 0 V ... 30 V (via DIP switch) | |
| max. input voltage | 33 V |
| Input resistance of voltage input | > 10 kΩ |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes |
| Voltage output signal | 0 V ... 5 V (via DIP switch) |
| 1 V ... 5 V (via DIP switch) | |
| -5 V ... 5 V (via DIP switch) | |
| 0 V ... 10 V (via DIP switch) | |
| 2 V ... 10 V (via DIP switch) | |
| -10 V ... 10 V (via DIP switch) | |
| Current output signal | 0 mA ... 20 mA (via DIP switch) |
| 4 mA ... 20 mA (via DIP switch) | |
| Max. output current | 22 mA |
| Short-circuit current | < 32 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | ≤ 600 Ω (at 20 mA) |
| Ripple | < 20 mVPP(at 600 Ω) |
| < 20 mVPP(at 600 Ω) |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Typical current consumption | 25 mA (Current output, at 24 V DC incl. load) |
| 54 mA (Current output, at 12 V DC incl. load) | |
| Power consumption | ≤ 800 mW (at IOUT= 20 mA, 9.6 V DC, 600 Ω load) |
Connection data
| Connection method | Screw connection |
|---|---|
| Stripping length | 10 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 1.5 mm² (with ferrule) |
| 0.2 mm² ... 2.5 mm² (without ferrule) | |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 12 (flexible) |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | ≤ 0.1 % (of final value) |
| Maximum temperature coefficient | 0.01 %/K |
| Limit frequency (3 dB) | 30 Hz (via DIP switch) |
| 5 kHz (via DIP switch) | |
| Step response (10-90%) | < 8.5 ms (with 30 Hz filter) |
| Protective circuit | Transient protection |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V |
| Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | gray |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27210100 |
|---|---|
| eCl@ss 4.1 | 27210100 |
| eCl@ss 5.0 | 27210100 |
| eCl@ss 5.1 | 27210100 |
| eCl@ss 6.0 | 27210100 |
| eCl@ss 7.0 | 27210120 |
| eCl@ss 8.0 | 27210120 |
| eCl@ss 9.0 | 27210120 |
UNSPSC
| UNSPSC 6.01 | 30211502 |
|---|---|
| UNSPSC 7.0901 | 39121004 |
| UNSPSC 11 | 39121004 |
| UNSPSC 12.01 | 39121004 |
| UNSPSC 13.2 | 39121008 |
| UNSPSC 18.0 | 39121008 |
| UNSPSC 19.0 | 39121008 |
| UNSPSC 20.0 | 39121008 |
| UNSPSC 21.0 | 39121008 |