View larger
MINI MCR-2-SPS-24-15 1033202 PHOENIX CONTACT Constant voltage source
MINI MCR-2-SPS-24-15
1033202
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for low-voltage switch technology
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Operating as a MINI MCR-2-SPS-24-15 1033202 PHOENIX CONTACT Constant voltage source, this electronic module delivers regulated electrical output for sensitive instrumentation circuits. Voltage sources maintain stable power delivery across varying input conditions, protecting automation loops from voltage fluctuations.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): Yes
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 1033202 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4055626537962 |
| Weight per Piece (excluding packing) | 106.720 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Output data
| Max. output voltage | 15 V DC |
|---|---|
| Output voltage with wire break | 15 V |
| Output current | ≤ 30 mA |
| Short-circuit current | > 35 mA |
| Ripple | < 20 mVPP(at 600 Ω) |
Power supply
| Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
|---|---|
| Typical current consumption | < 38.2 mA (24 V) |
| < 79.8 mA (12 V) | |
| Power consumption | < 900 mW (9.6 V DC) |
Connection data
| Connection method | Screw connection |
|---|---|
| Single conductor/terminal point, solid, with ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, with ferrule, max. | 1.5 mm² |
| Single conductor/terminal point, solid, without ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, without ferrule, max. | 2.5 mm² |
| Min. AWG conductor cross section, flexible | 24 |
| Max. AWG conductor cross section, flexible | 12 |
| Stripping length | 10 mm |
| Screw thread | M3 |
General
| Maximum transmission error | ≤ 0.4 % (of final value) |
|---|---|
| Maximum temperature coefficient | < 0.01 %/K |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V (effective) |
| Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | gray |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |