View larger
MCR-SLP-1-5-UI-0 2814359 PHOENIX CONTACT Current transducers
MCR-SLP-1-5-UI-0
2814359
PHOENIX CONTACT
1 Pcs.
Automation > Current value transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
MCR-SLP-1-5-UI-0 from Phoenix Contact is a precision current transducer engineered to translate primary electrical values into accurate analog outputs for control systems. These modules integrate seamlessly into electrical cabinets to provide continuous process variable monitoring and feedback. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Initial value measuring range current (EF008198): 0 A
- End value measuring range current (EF008266): 1 A
- Frequency rated current (EF005737): 50 Hz
- Type of analogy output (EF003958): 0-10 V
- Integrated configuration function (EF003064): No
- With switching output (EF005225): No
More info
▲Key Commercial Data
| Orderkey | 2814359 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 248 (C-5-2017) |
| GTIN | 4017918148447 |
| Weight per Piece (excluding packing) | 210.400 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 80 °C (non-condensing) |
| Maximum altitude | < 2000 m |
Input data
| Input | Current measuring input 1 A |
|---|---|
| Input current range | 0 A AC ... 1 A |
| Impulse form | Sine |
| Overload capacity | 2 x IN(5 min. at 60°C ambient temperature) |
| Surge strength | 50 A (1 s) |
| Permissible output range | 1.2 x IN |
| Nominal frequency fN | 50 Hz |
| Frequency measuring range | 45 Hz ... 60 Hz |
| Power dissipation | 1.6 VA (at IA= 20 mA) |
| Connection method | Screw connection |
| Input | Current measuring input 5 A |
| Input current range | 0 A AC ... 5 A |
| Impulse form | Sine |
| Overload capacity | 2 x IN(5 min. at 60°C ambient temperature) |
| Surge strength | 100 A (1 s) |
| Permissible output range | 1.2 x IN |
| Nominal frequency fN | 50 Hz |
| Frequency measuring range | 45 Hz ... 60 Hz |
| Power dissipation | 2.2 VA (I = 20 mA) |
| Connection method | Screw connection |
Output data
| Output name | Voltage output |
|---|---|
| Voltage output signal | 0 V ... 10 V |
| Max. output voltage | 20 V |
| Load/output load voltage output | > 100 kΩ |
| Ripple | < 50 mVPP |
| Output name | Current output |
| Current output signal | 0 mA ... 20 mA |
| Max. output current | 30 mA |
| Load/output load current output | < 750 Ω |
| Ripple | < 50 mVPP |
| Residual ripple, in reference to the measured value | 0.5 % (pp of measured value) |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 8 mm |
| Screw thread | M3 |
General
| Maximum transmission error | < 0.5 % (of final value) |
|---|---|
| Maximum temperature coefficient | < 0.015 %/K |
| Step response (10-90%) | < 200 ms |
| Test voltage | 3.5 kV |
| Protective circuit | Transient protection in the output Suppressor diode |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V AC (to earth) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | Polyamide PA non-reinforced |
| Mounting position | < 50 °C: any; > 50 °C: vertical (installation on horizontal DIN rail) |
| Conformance | CE-compliant |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Connection in acc. with standard | CUL |
| Conformance | CE-compliant |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|