PHOENIX CONTACT MACX MCR-SL-RPSSI-2I MACX MCR-SL-RPSSI-2I 2924825 PHOENIX CONTACT Repeater power supply View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MACX MCR-SL-RPSSI-2I 2924825 PHOENIX CONTACT Repeater power supply

MACX MCR-SL-RPSSI-2I

2924825

PHOENIX CONTACT

1 Pcs.

Repeater power supply HART Transparent Power Transducer Power Signal Conditioner and Input Signal Conditioner. Transfers 0/4 powered or activated signals... 20 mA galvanically separated from the field in two charges. 4-way galvanic separation, screw connection, SIL, PL.

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact MACX MCR-SL-RPSSI-2I repeater power supplies supply 2-wire transmitters in hazardous and safe areas while transmitting the proportional 4-20 mA analog signal to control systems. They ensure reliable signal transmission and galvanic separation in complex process instrumentation loops. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated supply voltage DC (EF007078): 19.2 V
  • Number of input ranges -60 mV ... +60 mV (EF006927): 0
  • Number of input ranges -100 mV ... +100 mV (EF006912): 0
  • Number of input ranges -300 mV ... +300 mV (EF006920): 0
  • Number of input ranges -500 mV ... +500 mV (EF006926): 0
  • Number of input ranges -1 V ... +1 V (EF006906): 0
  • Number of input ranges -2 V ... +2 V (EF006913): 0
  • Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
  • Number of input ranges -5 V ... +5 V (EF006923): 0
  • Number of input ranges -10 V ... +10 V (EF006909): 0
  • Number of input ranges -20 V ... +20 V (EF006917): 0
  • Number of input ranges 0 mV ... 60 mV (EF006905): 0
  • Number of input ranges 0 mV ... 100 mV (EF006893): 0
  • Number of input ranges 0 mV ... 200 mV (EF006898): 0
  • Number of input ranges 0 mV ... 300 mV (EF006901): 0
  • Number of input ranges 0 mV ... 500 mV (EF006904): 0

More info

▲

Key Commercial Data

Orderkey2924825
Packing unit1 pc
Catalog pagePage 121 (C-5-2017)
GTIN4046356572040
Weight per Piece (excluding packing)156.000 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width12.5 mm
Height112.5 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
-20 °C ... 70 °C (any mounting position, module distance 5 mm, MTBF reduction factor 2.5, not assessed by UL)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2

Input data

Signal inputRepeater power supply operation
Current input signal4 mA ... 20 mA
Transmitter supply voltage> 21.5 V (20 mA)
> 21 V (23 mA)
Underload/overload signal range0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal inputSignal conditioner operation
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop< 3.9 V (in input isolating amplifier operation)
Underload/overload signal range0 mA ... 24 mA (Extended transmission range for diagnostics)

Output data

Signal outputRepeater power supply operation
Current output signal4 mA ... 20 mA (active)
0 mA ... 20 mA
Load/output load current output< 450 Ω (20 mA)
< 380 Ω (23 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal outputSignal conditioner operation
Current output signal0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
Load/output load current output< 450 Ω (20 mA)
< 380 Ω (23 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)

Power supply

DesignationRepeater power supply operation
Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption< 75 mA (24 V DC / 20 mA)
Power dissipation< 1.45 W (24 V DC/ 20 mA)
DesignationSignal conditioner operation
Nominal supply voltage range19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption< 46 mA (24 V DC / 20 mA)
Power dissipation< 1.2 W (24 V DC / 20 mA)

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

No. of channels1
Maximum transmission error< 0.1 % (of final value)
Transmission error, typical< 0.05 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Step response (10-90%)1.3 ms (for jump 4 mA ... 20 mA, typical)
Status displayGreen LED (PWR supply voltage)
Flammability rating according to UL 94V0
Electromagnetic compatibilityConformance with EMC directive
Interference emissionEN 61000-6-4
Housing materialPA 6.6-FR
Colorgray
DesignationInput/output/power supply
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationOutput 1/output 2
Electrical isolation1.5 kV AC (50 Hz, 1 min., test voltage)
ConformanceCE-compliant, additionally EN 61326-1
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
SIL2

Data communication (bypass)

HART functionYes
Protocols supportedHART

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value3 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value3 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value3 %

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Flammability rating according to UL 94V0
ConformanceCE-compliant, additionally EN 61326-1
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCA
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.