View larger
MACX MCR-SL-RPSSI-2I 2924825 PHOENIX CONTACT Repeater power supply
MACX MCR-SL-RPSSI-2I
2924825
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MACX MCR-SL-RPSSI-2I repeater power supplies supply 2-wire transmitters in hazardous and safe areas while transmitting the proportional 4-20 mA analog signal to control systems. They ensure reliable signal transmission and galvanic separation in complex process instrumentation loops. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 19.2 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
More info
▲Key Commercial Data
| Orderkey | 2924825 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 121 (C-5-2017) |
| GTIN | 4046356572040 |
| Weight per Piece (excluding packing) | 156.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) |
|---|---|
| -20 °C ... 70 °C (any mounting position, module distance 5 mm, MTBF reduction factor 2.5, not assessed by UL) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 |
Input data
| Signal input | Repeater power supply operation |
|---|---|
| Current input signal | 4 mA ... 20 mA |
| Transmitter supply voltage | > 21.5 V (20 mA) |
| > 21 V (23 mA) | |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
| Signal input | Signal conditioner operation |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Voltage drop | < 3.9 V (in input isolating amplifier operation) |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Output data
| Signal output | Repeater power supply operation |
|---|---|
| Current output signal | 4 mA ... 20 mA (active) |
| 0 mA ... 20 mA | |
| Load/output load current output | < 450 Ω (20 mA) |
| < 380 Ω (23 mA) | |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| ≥ 23 mA (Cable short-circuit in the input) | |
| Signal output | Signal conditioner operation |
| Current output signal | 0 mA ... 20 mA (active) |
| 4 mA ... 20 mA (active) | |
| Load/output load current output | < 450 Ω (20 mA) |
| < 380 Ω (23 mA) | |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| 0 mA (Cable short-circuit in the input) |
Power supply
| Designation | Repeater power supply operation |
|---|---|
| Nominal supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Max. current consumption | < 75 mA (24 V DC / 20 mA) |
| Power dissipation | < 1.45 W (24 V DC/ 20 mA) |
| Designation | Signal conditioner operation |
| Nominal supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Max. current consumption | < 46 mA (24 V DC / 20 mA) |
| Power dissipation | < 1.2 W (24 V DC / 20 mA) |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Connection method | Screw connection |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | < 0.1 % (of final value) |
| Transmission error, typical | < 0.05 % (of final value) |
| Maximum temperature coefficient | < 0.01 %/K |
| Step response (10-90%) | 1.3 ms (for jump 4 mA ... 20 mA, typical) |
| Status display | Green LED (PWR supply voltage) |
| Flammability rating according to UL 94 | V0 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Input/output/power supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Output 1/output 2 |
| Electrical isolation | 1.5 kV AC (50 Hz, 1 min., test voltage) |
| Conformance | CE-compliant, additionally EN 61326-1 |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 61010 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC T4 | |
| SIL | 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 3 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 3 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 3 % |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326-1 |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 61010 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC T4 | |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |