View larger
QUINT4-S-ORING/12-24DC/1X40 2907752 PHOENIX CONTACT Redundancy module
QUINT4-S-ORING/12-24DC/1X40
2907752
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection module
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact QUINT4-S-ORING/12-24DC/1X40 redundancy module provides reliable decoupling for power supply units in critical automation setups, helping to prevent system downtime by separating parallel power paths. These units are commonly integrated into industrial control panels to ensure uninterrupted power distribution and safeguard sensitive loads against supply failures.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- DC operation Nominal input voltage range: 12 V DC ... 24 V DC
- Input voltage range: 8 V DC ... 30 V DC
- Typical national grid voltage: 12 V DC
- Voltage type of supply voltage: DC
- Current consumption: 40 A
- Static Boost (I Stat.Boost ): 45 A
- Dynamic Boost (I Dyn.Boost ): 60 A (5 s)
- Selective Fuse Breaking (I SFB ): 215 A (15 ms)
- Reverse polarity protection: < yes60 V
- Nominal input current (I N ): 40 A (-40 °C ... 60 °C)
- Input current I Static: 45 A (40 °C)
- Input current I Dynamic: 60 A (5 s)
- Input current I SFB: 215 A (15 ms)
- Transient surge protection: Varistor
- Voltage drop, input/output: 0.1 V
- Efficiency: typ. 99.1 % (12 V DC)
More info
▲| DC operation | |
| Nominal input voltage range | 12 V DC ... 24 V DC |
| Input voltage range | 8 V DC ... 30 V DC |
| Typical national grid voltage | 12 V DC |
| 24 V DC | |
| Voltage type of supply voltage | DC |
| Current consumption | 40 A |
| Static Boost (IStat.Boost) | 45 A |
| Dynamic Boost (IDyn.Boost) | 60 A (5 s) |
| Selective Fuse Breaking (ISFB) | 215 A (15 ms) |
| Reverse polarity protection | < yes60 V |
| Nominal input current (IN) | 40 A (-40 °C ... 60 °C) |
| Input current IStatic | 45 A (40 °C) |
| Input current IDynamic | 60 A (5 s) |
| Input current ISFB | 215 A (15 ms) |
| Transient surge protection | Varistor |
| Voltage drop, input/output | 0.1 V |
| Efficiency | typ. 99.1 % (12 V DC) |
| typ. 99.3 % (24 V DC) | |
| Nominal output voltage | UIn- 0.1 V |
| Nominal output current (IN) | 40 A |
| Static Boost (IStat.Boost) | 45 A |
| Dynamic Boost (IDyn.Boost) | 60 A (5 s) |
| Selective Fuse Breaking (ISFB) | 215 A (15 ms) |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Power loss nominal load max. | 6.5 W (IOUT= 40 A) |
| 6 W (IOUT= 40 A) | |
| Connection in series | no |
| Signal: OK, 13/14 | |
| Output description | Group contact |
| Maximum switching voltage | max. 30 V AC/DC |
| Maximum inrush current | ≤ 100 mA (short-circuit-proof) |
| Signal relay 13/14 | |
| Default | open |
| Additional text | UIN |
| Signal relay 13/14 | |
| Default | closed |
| Additional text | UIN> 8 V DC |
| Signal relay 13/14 | |
| Default | open |
| Additional text | Redundancy module defective |
| Input | |
| Connection method | Screw connection |
| Conductor cross section, rigid min. | 0.5 mm² |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 16 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.5 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 16 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.2 Nm |
| Tightening torque max | 1.5 Nm |
| Output | |
| Connection method | Screw connection |
| Conductor cross section, rigid min. | 0.5 mm² |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 16 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.5 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 16 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.2 Nm |
| Tightening torque max | 1.5 Nm |
| Signal | |
| Connection method | Push-in connection |
| Conductor cross section, rigid min. | 0.2 mm² |
| Conductor cross section, rigid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.2 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 0.75 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.2 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Types of signaling | Relay contact, floating, current limited |
| Signal output: OK, 13/14 | |
| UIn< 8 V DC | LED off, input voltage not present or short circuit at redundancy module output |
| UIn> 8 V DC | LED lights up green, input voltage present |
| Redundancy modul faulty | LED lights up red, redundancy module needs to be factory tested |
| Insulation voltage input, output / housing | 500 V DC |
| Product type | Redundancy module |
| Product family | QUINT S-ORING |
| MTBF (IEC 61709, SN 29500) | > 25297000 h (25 °C) |
| > 15153000 h (40 °C) | |
| > 7449000 h (60 °C) | |
| LED | yes |
| Data management status | |
| Article revision | 03 |
| Insulation characteristics | |
| Protection class | III |
| Degree of pollution | 2 |
| Life expectancy (electrolytic capacitors) | |
| Current | 40 A |
| Temperature | 40 °C |
| Time | 186000 h |
| Additional text | 12 V DC |
| Life expectancy (electrolytic capacitors) | |
| Current | 40 A |
| Temperature | 40 °C |
| Time | 123000 h |
| Additional text | 24 V DC |
| Dimensional drawing | |
| Width | 32 mm |
| Height | 130 mm |
| Depth | 125 mm |
| Installation dimensions | |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 40 mm / 20 mm |
| Alternative assembly | |
| Width | 122 mm |
| Height | 130 mm |
| Depth | 35 mm |
| Mounting type | DIN rail mounting |
| Assembly note | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
| Housing material | Metal |
| Housing material | Aluminum / stainless steel |
| Type of housing | Aluminum (AlMg3) |
| Hood version | Galvanized sheet steel, free from chrome (VI) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Shipbuilding approval | DNV GL |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Conformity/Approvals | |
| SIL in accordance with IEC 61508 | 0 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| EMC requirements for noise emission | EN 61000-6-3 |
| EN 61000-6-4 | |
| EMC requirements for noise immunity | EN 61000-6-1 |
| EN 61000-6-2 | |
| Conducted noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station) |
| Noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| DNV GL conducted interference | Class A |
| Additional text | Area power distribution |
| DNV GL noise radiation | Class B |
| Additional text | Bridge and deck area |
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 |
| Electrostatic discharge | |
| Contact discharge | 8 kV (Test Level 4) |
| Discharge in air | 15 kV (Test Level 4) |
| Comments | Criterion B |
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 |
| Electromagnetic HF field | |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 20 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Comments | Criterion A |
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 |
| Fast transients (burst) | |
| Input | 2 kV (Test Level 4 - asymmetrical) |
| Output | 2 kV (Test Level 4 - asymmetrical) |
| Signal | 2 kV (Test Level 4 - asymmetrical) |
| Comments | Criterion A |
| Surge voltage load (surge) | |
| Standards/regulations | EN 61000-4-5 |
| Surge voltage load (surge) | |
| Input | 1 kV (Test Level 3 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) | |
| Output | 0.5 kV (Test Level 1 - symmetrical) |
| 0.5 kV (Test Level 1 - asymmetrical) | |
| Signal | 0.5 kV (Test Level 1 - asymmetrical) |
| Comments | Criterion B |
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 |
| Conducted interference | |
| I/O/S | asymmetrical |
| Frequency range | 0.15 MHz ... 80 MHz |
| Comments | Criterion A |
| Voltage | 10 V (Test Level 3) |
| Power frequency magnetic field | |
| Standards/regulations | EN 61000-4-8 |
| Frequency | 16.67 Hz |
| 50 Hz | |
| 60 Hz | |
| Test field strength | 30 A/m |
| Additional text | 60 s |
| Comments | Criterion A |
| Criteria | |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |