View larger
TTC-6-TVSD-C-24DC-UT-I 2906831 PHOENIX CONTACT Fine surge protection with integrated status indicator for a ..
TTC-6-TVSD-C-24DC-UT-I
2906831
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Offering fine surge protection with integrated status indicator for a .. application, the Phoenix Contact TTC-6-TVSD-C-24DC-UT-I 2906831 module guards sensitive automation electronics against destructive voltage peaks. Compact DIN rail components like this ensure high-density packaging without sacrificing reliability in industrial control panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for MCR technology
- Product family: TERMITRAB complete
- IEC test classification: C3
- Type: DIN rail module, one-piece
- Surge protection fault message: optical
- Data management status Article revision: 08
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 24 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm ... 0.6 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Width: 6.2 mm
More info
▲| Product type | Surge protection for MCR technology |
| Product family | TERMITRAB complete |
| IEC test classification | C3 |
| Type | DIN rail module, one-piece |
| Surge protection fault message | optical |
| Data management status | |
| Article revision | 08 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Dimensional drawing | |
| Width | 6.2 mm |
| Height | 92 mm |
| Depth | 69.5 mm (incl. DIN rail 7.5 mm) |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V-0 |
| Insulating material | PBT |
| Housing material | PBT |
| Mechanical data | |
| Open side panel | Yes |
| Direction of action | Line-Earth Ground |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 10 A (60 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-ground) | 150 A |
| Voltage protection level Up(line-earth) | ≤ 50 V (C3 - 25 A) |
| ≤ 50 V (C3 - 30 A) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 520 kHz/150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system | typ. 1.7 MHz |
| Capacity (Core-Earth) | 1.5 nF |
| Resistance per path | ≤ 100 mΩ |
| Surge protection fault message | optical |
| Impulse durability (line-earth) | C3 - 30 A |
| Ambient conditions | |
| Degree of protection | IP20 (with end cover) |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| EN 61643-21 | |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 + A2:2013 |
| Mounting type | DIN rail: 35 mm |