View larger
MINI MCR-SL-2CP-I-I 2864655 PHOENIX CONTACT Loop-powered isolators
MINI MCR-SL-2CP-I-I
2864655
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Functioning as a passive isolation barrier, the MINI MCR-SL-2CP-I-I Loop-powered isolators by Phoenix Contact operates directly from the current loop without requiring an external power supply. These isolators protect delicate input cards and eliminate common-mode voltages in industrial measurement loops.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
- Number of input ranges 0 V ... 1 V (EF006890): 0
More info
▲Key Commercial Data
| Orderkey | 2864655 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 101 (C-7-2015) |
| GTIN | 4017918974893 |
| Weight per Piece (excluding packing) | 61.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Input data
| Description of the input | Current input |
|---|---|
| Number of inputs | 2 |
| Configurable/programmable | no |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| max. input voltage | 18 V |
| Max. input current | 40 mA |
| Response current | approx. 190 µA |
| Input voltage limitation | < 2 V (20 mA) |
| Voltage dissipation | 1.9 V (I = 20 mA) |
Output data
| Output name | Current output |
|---|---|
| Number of outputs | 2 |
| Configurable/programmable | no |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Load/output load current output | < 600 Ω (at I = 20 mA output signal) |
| Ripple | < 10 mVrms(at 600 Ω) |
| Transmission Behavior | 1:1 to input signal |
Power supply
| Supply voltage range | no separate supply voltage necessary |
|---|---|
| Power consumption | 34 mW (per channel) |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 12 mm |
| Screw thread | M3 |
General
| No. of channels | 2 |
|---|---|
| Maximum transmission error | ≤ 0.1 % (of final value) |
| Maximum temperature coefficient | ≤ 0.002 %/K (of measured value / 100 Ω load) |
| Temperature coefficient, typical | < 0.002 %/K (of measured value / 100 Ω load) |
| Additional error, load-dependent | < 0.03 % (of measured value / 100 Ω load) |
| Limit frequency (3 dB) | 75 Hz |
| Step response (10-90%) | 5 ms (at 600 Ω load) |
| Electrical isolation | Basic insulation according to EN 61010 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 50 V AC/DC |
| Test voltage input/output | 1.5 kV (50 Hz, 1 min.) |
| Test voltage channel/channel | 1.5 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA II T6 X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| GL | GL EMC 2 D |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Evaluation criterion | A |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Evaluation criterion | B |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Evaluation criterion | A |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Evaluation criterion | A |
| Standards/regulations | EN 61000-4-4 |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Evaluation criterion | A |
| Electrical isolation | Basic insulation according to EN 61010 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA II T6 X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| GL | GL EMC 2 D |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |