View larger
MCR-S-1-5-UI-DCI-NC 2814715 PHOENIX CONTACT Current transducers
MCR-S-1-5-UI-DCI-NC
2814715
PHOENIX CONTACT
1 Pcs.
Automation > Current value transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for precise electrical surveillance, the Phoenix Contact MCR-S-1-5-UI-DCI-NC Current transducers device monitors circuit loads within industrial switchgear. These instruments scale heavy amperage metrics down to safe, manageable signal levels required by monitoring instrumentation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2814715
- Packing unit: 1 pc
- Catalog page: Page 242 (C-5-2017)
- GTIN: 4017918169275
- Weight per Piece (excluding packing): 134.080 g
- Custom tariff number: 85437090
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Width: 22.5 mm
- Height: 99 mm
- Depth: 114.5 mm
- Ambient temperature (operation): -20 °C ... 60 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Maximum altitude: < 2000 m
- Input: Current measuring input
- Number of inputs: 3
More info
▲Key Commercial Data
| Orderkey | 2814715 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 242 (C-5-2017) |
| GTIN | 4017918169275 |
| Weight per Piece (excluding packing) | 134.080 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | < 2000 m |
Input data
| Input | Current measuring input |
|---|---|
| Number of inputs | 3 |
| Configurable/programmable | Yes, unconfigured |
| Input current range | 0 A ... 11 A (AC/DC) |
| Operate threshold | 2 % (of measuring range nominal value 1/5/10 A) |
| Setting range for min. input current | 0 A ... 200 mA |
| Setting range for max. input current | 0 A ... 11 A |
| Impulse form | AC, DC or distorted currents |
| Overload capacity | 2 x IN (continuous) |
| Surge strength | 20 x IN(1 s) |
| Frequency measuring range | 15 Hz ... 400 Hz |
| Connection method | Screw connection |
Output data
| Output name | Voltage output / current output |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage output signal | 0 V ... 10 V |
| 2 V ... 10 V | |
| -10 V ... 10 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| -5 V ... 5 V | |
| 10 V ... 0 V | |
| 10 V ... 2 V | |
| 10 V ... -10 V | |
| 5 V ... 0 V | |
| 5 V ... 1 V | |
| 5 V ... -5 V | |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| 20 mA ... 0 mA | |
| 20 mA ... 4 mA | |
| Load/output load voltage output | > 10 kΩ |
| Load/output load current output | < 500 Ω |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 8 mm |
| Screw thread | M3 |
General
| Maximum transmission error | < 0.5 % (of nominal range value under nominal conditions) |
|---|---|
| Temperature coefficient, typical | < 0.025 %/K |
| Step response (10-90%) | 330 ms (with AC) |
| 40 ms (with DC) | |
| Status display | Green LED |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V AC (to earth) |
| Test voltage input/output | 4 kV (50 Hz, 1 min.) |
| Test voltage input/power supply | 4 kV (50 Hz, 1 min.) |
| Test voltage output/power supply | 500 V (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Color | green |
| Housing material | Polyamide PA non-reinforced |
| Mounting position | any |
| Conformance | CE-compliant |
| UL, USA/Canada | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
| Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Connection in acc. with standard | CUL |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Conformance | CE-compliant |
| UL, USA/Canada | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
| Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |