View larger
Images are for illustrative purposes only. Please refer to data sheet for details
MACX MCR-TC-I 1050228 PHOENIX CONTACT Temperature transducer: converts signals from thermocouples and mV sou..
MACX MCR-TC-I
1050228
PHOENIX CONTACT
1 Pcs.
Temperature transducer: converts signals from thermocouples and mV sources into 0/4…20 mA signals. Freely programmable, 3-way electrical isolation, screw connection, SIL.
Temperature converter: transforms signals from thermocouples and mV sources into 0/4-20 mA signals. Free programming, 3-way galvanic separation, screw connection, SIL.
Automation > Temperature transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MACX MCR-TC-I temperature transducer is designed to convert signals from thermocouples and millivolt sources into standardized process signals while maintaining functional safety compliance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Product type: Temperature transmitter
- Product family: MACX Analog
- Application: Temperature
- No. of channels: 1
- Type: Signal conditioners with SIL functional safety
- Configuration: Software
- Data management status Article revision: 06
- Insulation characteristics GB Standard Overvoltage category: II
- Pollution degree: 2
- Electrical isolation: 3-way isolation
- Cold point error, max.: ± 2 K
- Step response (0–99%): 1 s
- Temperature coefficient, typical: 0.01 %/K
- Transmission error, typical: 0.1 % (For full identification of transmission errors, see the data sheet)
- Test voltage: 2.5 kV AC (50 Hz, 60 s)
More info
▲Technical data
Notes
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
| Product type | Temperature transmitter |
| Product family | MACX Analog |
| Application | Temperature |
| No. of channels | 1 |
| Type | Signal conditioners with SIL functional safety |
| Configuration | Software |
| Data management status | |
| Article revision | 06 |
| Insulation characteristics: GB Standard | |
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Electrical isolation | 3-way isolation |
| Cold point error, max. | ± 2 K |
| Step response (0–99%) | 1 s |
| ≤ 1.7 s | |
| Temperature coefficient, typical | 0.01 %/K |
| Transmission error, typical | 0.1 % (For full identification of transmission errors, see the data sheet) |
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 300 Vrms |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
| Electrical isolation Input/output | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
| Electrical isolation Input/power supply | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
| Supply | |
| Nominal supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Max. current consumption | < 40 mA (24 V DC) |
| Power dissipation | ≤ 0.76 W |
| Power consumption | ≤ 1 W |
Input data
| Signal | |
| Number of inputs | 1 |
| Input signal | Temperature |
| Voltage | |
| Measurement | |
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, C, D, A-1, A-2, A-3, M, Lr |
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Sensor type: | 500 °C ... 1820 °C |
| -230 °C ... 1000 °C | |
| -210 °C ... 1200 °C | |
| -250 °C ... 1372 °C | |
| -200 °C ... 1300 °C | |
| -50 °C ... 1768 °C | |
| -50 °C ... 1768 °C | |
| -200 °C ... 400 °C | |
| -200 °C ... 900 °C | |
| -200 °C ... 600 °C | |
| 0 °C ... 2315 °C | |
| 0 °C ... 2315 °C | |
| 0 °C ... 2500 °C | |
| 0 °C ... 1800 °C | |
| 0 °C ... 1800 °C | |
| -200 °C ... 100 °C | |
| -200 °C ... 800 °C | |
| Linear mV signal range | -1000 mV ... 1000 mV |
| Temperature measuring range | Min. 50 K with thermocouple, 10% of the nominal span of the respective range with mV sources |
Output data
| Signal: Current | |
| Number of outputs | 1 |
| Configurable/programmable | Yes |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA (SIL) | |
| Load/output load current output | ≤ 600 Ω |
| Output ripple (current) | < 15 µAPP |
| < 10 µArms | |
| Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Connection data
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Test socket | |
| Max. diameter | 2 mm |
Ex data
| Ex installation (EPL) | Gc |
| Div. 2 |
Signaling
| Status display | Green LED (supply voltage) |
| Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR) | |
| Red LED, flashing 1.2 Hz (service operation, ERR) | |
| Red LED, permanently on (module error, ERR) |
Dimensions
| Dimensional drawing | |
| Width | 12.5 mm |
| Height | 112.5 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing material | PA 6.6-FR |
Environmental and real-life conditions
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Test voltage | 2.5 kV |
| Rated insulation voltage | 300 Vrms |
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m ... 3000 m |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| Test voltage | 2.25 kV |
| Rated insulation voltage | 150 Vrms |
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m ... 4000 m |
| Ambient temperature (operation) | -40 °C ... 55 °C |
| Test voltage | 2 kV |
| Rated insulation voltage | 150 Vrms |
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m ... 5000 m |
| Ambient temperature (operation) | -40 °C ... 49 °C |
| Test voltage | 1.75 kV |
| Rated insulation voltage | 150 Vrms |
Approvals
| CE | |
| Certificate | CE-compliant |
| Note | and EN 61326 |
| ATEX | |
| Identification | II 3 G Ex ec ic IIC T4 Gc |
| Certificate | PxCIF19ATEX1050192X |
| UKCA Ex (UKEX) | |
| Identification | II 3 G Ex ec ic IIC T4 Gc |
| Certificate | PxCIF21UKEX1050192X |
| IECEx | |
| Identification | Ex ec ic IIC T4 Gc |
| Certificate | IECEx IBE 19.0001 X |
| CCC / China-Ex | |
| Identification | Ex nA ic IIC T4 Gc |
| Certificate | NEPSI GYJ20.1305X |
| UL, USA/Canada | |
| Identification | UL 61010 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC T4 | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA00000AG |
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 |
| Certificate | SEBS-A.150520/17, V2.0 |
| EAC Ex | |
| Identification | 2Ex ec ic IIC T4 Gc |
| Certificate | BY/112 02.01 TP012 103.01 00082 |
| DNV GL data | |
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Noise emission | EN 61000-6-4 |
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 1 % |
| Fast transients (burst) | |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 1 % |
| Conducted interference | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 1 % |
Standards and regulations
| Electrical isolation | 3-way isolation |
| GB Standard | |
| Standards/regulations | GB 3836.1 |
| GB 3836.4 | |
| GB 3836.8 | |
Mounting
| Mounting type | DIN rail mounting |