View larger
MACX MCR-SL-UI-REL 2906169 PHOENIX CONTACT Limit value switch with input for active current and voltage sign..
MACX MCR-SL-UI-REL
2906169
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MACX MCR-SL-UI-REL limit value switches monitor analog input signals and trigger relay outputs when preset upper or lower thresholds are exceeded. They provide reliable threshold detection and equipment protection across various automation and process control layouts. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
- Number of input ranges 0 V ... 1 V (EF006890): 0
More info
▲Key Commercial Data
| Orderkey | 2906169 |
|---|---|
| Packing unit | 1 |
| Catalog page | Page 140 (C-5-2019) |
| GTIN | 4055626043760 |
| Custom tariff number | 85437090 |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
| Voltage input signal | 0.1 V ... 10 V |
|---|---|
| Current input signal | 0.2 mA ... 20 mA |
| 0.18 mA ... 21 mA (Maximum range) | |
| Input resistance of voltage input | > 100 kΩ |
| Input resistance current input | < 28 Ω |
| Switching hysteresis | off: approx. 0.5 %, on: approx. 1 % |
| Line fault detection | Break U |
| Short circuit U > 10.8 V, I > 21.1 mA |
Output data
| Output name | Relay output |
|---|---|
| Contact type | 1 PDT |
| Contact material | AgSnO2, hard gold-plated |
| Max. switching current | ≤ 4 A AC (cos phi = 1) |
| ≤ 1 A DC (ohmic load, 24 V DC, 50 mW) | |
| ≤ 0.2 A DC (ohmic load, 120 V DC) | |
| Mechanical service life | ≤ 107cycles |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 9.6 V DC ... 30 V DC (12 V DC ... 24 V DC (-20 % ... +25 %)) |
| Typical current consumption | 38 mA (24 V DC) |
| Max. current consumption | 90 mA (10 V DC) |
| Power dissipation | < 0.9 W |
| Power consumption | ≤ 1.2 W |
General
| Maximum transmission error | 0.1 % |
|---|---|
| Maximum temperature coefficient | 0.01 %/K |
| Step response (0–99%) | ≤ 22 ms |
| Status display | Green LED (supply voltage, PWR) |
| Red LED, flashing (line, sensor error, ERR) | |
| Yellow LED (switching output) | |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/output/supply, DIN rail connector |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Input/supply, DIN rail connector |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II 3 G Ex ec nC IIC T4 Gc |
| IECEx | Ex ec nC IIC T4 Gc |
| UL, USA/Canada | UL applied for |
| SIL | 2 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II 3 G Ex ec nC IIC T4 Gc |
| IECEx | Ex ec nC IIC T4 Gc |
| UL, USA/Canada | UL applied for |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27210100 |
|---|---|
| eCl@ss 4.1 | 27210100 |
| eCl@ss 5.0 | 27210100 |
| eCl@ss 5.1 | 27210100 |
| eCl@ss 6.0 | 27210100 |
| eCl@ss 7.0 | 27210120 |
| eCl@ss 8.0 | 27210120 |
| eCl@ss 9.0 | 27210120 |