View larger
MACX MCR-SL-2I-2I-ILP-SP 2905281 PHOENIX CONTACT Loop-powered isolators
MACX MCR-SL-2I-2I-ILP-SP
2905281
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A loop-powered isolator such as the MACX MCR-SL-2I-2I-ILP-SP 2905281 Phoenix Contact Loop-powered isolators provides galvanic isolation for standard analog current loops in industrial process control systems. These modules prevent ground loops and protect downstream monitoring equipment from electrical surges without requiring an auxiliary external power supply.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Signal conditioner
- Product family: MACX Analog
- No. of channels: 2
- Type: Signal conditioners with SIL functional safety
- Data management status Article revision: 04
- Insulation characteristics Overvoltage category: II
- Pollution degree: 2
- Electrical isolation: 2-way isolation
- Signal transmission behavior: In = Out
- Maximum temperature coefficient: ≤ 0.002 %/K (of measured value / 100 Ω load)
- Transmission error, typical: 0.08 % (of final value)
- Test voltage: 2.5 kV AC (50 Hz, 60 s)
- Insulation: Safe isolation in accordance with IEC/EN 61010-1
- Supply Supply voltage range: loop-powered, no external supply necessary
- Signal: Current Number of inputs: 2
- Configurable/programmable: no
More info
▲| Product type | Signal conditioner |
| Product family | MACX Analog |
| No. of channels | 2 |
| Type | Signal conditioners with SIL functional safety |
| Data management status | |
| Article revision | 04 |
| Insulation characteristics | |
| Overvoltage category | II |
| Pollution degree | 2 |
| Electrical isolation | 2-way isolation |
| Signal transmission behavior | In = Out |
| Maximum temperature coefficient | ≤ 0.002 %/K (of measured value / 100 Ω load) |
| Transmission error, typical | 0.08 % (of final value) |
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 300 Vrms |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
| Supply | |
| Supply voltage range | loop-powered, no external supply necessary |
| Signal: Current | |
| Number of inputs | 2 |
| Configurable/programmable | no |
| Max. voltage input signal | < 30.5 V |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Input voltage limitation | 30.5 V |
| Voltage dissipation | 2.9 V (I = 20 mA) |
| Step response (10-90%) | 5 ms (500 Ω load) |
| Additional error, load-dependent | 0.022 % (of measured value / 100 Ω load) |
| Response current | approx. 50 µA |
| Signal: Current | |
| Number of outputs | 2 |
| Configurable/programmable | no |
| Max. voltage output signal | 27.5 V |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Load/output load current output | ≤ 1375 Ω (I = 20 mA) |
| Residual ripple | < 10 mVrms(500 Ω load) |
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Test socket | |
| Max. diameter | 2.3 mm |
| Ex installation (EPL) | Gc |
| Div. 2 |
| Dimensional drawing | |
| Width | 12.5 mm |
| Height | 116 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing material | PA 6.6-FR |
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | < 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| CE | |
| Certificate | CE-compliant |
| Note | and EN 61326-1 |
| ATEX | |
| Identification | II 3 G Ex nA IIC T4 Gc X |
| UKCA Ex (UKEX) | |
| Identification | II 3 G Ex nA IIC T4 Gc X |
| Certificate | PxCIF21UKEX2905278X |
| UL, USA/Canada | |
| Identification | UL 61010 Listed |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC T4 | |
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 3 |
| Certificate | 968/FSP 1200.01/21 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise immunity | EN 61326-1 |
| Noise emission | EN 61000-6-4 |
| Electrical isolation | 2-way isolation |
| Mounting type | DIN rail mounting |