PHOENIX CONTACT MACX MCR-SL-2I-2I-ILP MACX MCR-SL-2I-2I-ILP 2905280 PHOENIX CONTACT Separator 2-way powered loop input two-channel connection tech.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MACX MCR-SL-2I-2I-ILP 2905280 PHOENIX CONTACT Separator 2-way powered loop input two-channel connection tech..

MACX MCR-SL-2I-2I-ILP

2905280

PHOENIX CONTACT

1 Pcs.

Separator 2-way powered loop input two-channel connection technology plug-in for the galvanic separation of analog signals. Input signal = output signal: 0(4)mA ... 20 mA. Connection technology screw. 2-way splitter powered by 2-channel input loop with plug-in connection technology for galvanic separation of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. Screw connection technology. 2-channel input loop-powered 2-way isolator with plug-in connection technology for the electrical isolation of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. Screw connection technology.

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Safe galvanic separation of standard current signals in safety-instrumented systems relies upon a Phoenix Contact MACX MCR-SL-2I-2I-ILP separator 2-way powered loop input two-channel connection tech. These loop-powered units pass analog values reliably without external power requirements, protecting control loops from high common-mode voltages and electrical noise.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Signal conditioner
  • Product family: MACX Analog
  • No. of channels: 2
  • Type: Signal conditioners with SIL functional safety
  • Data management status Article revision: 04
  • Insulation characteristics Overvoltage category: II
  • Pollution degree: 2
  • Electrical isolation: 2-way isolation
  • Signal transmission behavior: In = Out
  • Maximum temperature coefficient: ≤ 0.002 %/K (of measured value / 100 Ω load)
  • Transmission error, typical: 0.08 % (of final value)
  • Test voltage: 2.5 kV AC (50 Hz, 60 s)
  • Insulation: Safe isolation in accordance with IEC/EN 61010-1
  • Supply Supply voltage range: loop-powered, no external supply necessary
  • Signal: Current Number of inputs: 2
  • Configurable/programmable: no

More info

▲
Technical data

Product properties
Product typeSignal conditioner
Product familyMACX Analog
No. of channels2
TypeSignal conditioners with SIL functional safety
Data management status
Article revision04
Insulation characteristics
Overvoltage categoryII
Pollution degree2

Electrical properties
Electrical isolation2-way isolation
Signal transmission behaviorIn = Out
Maximum temperature coefficient≤ 0.002 %/K (of measured value / 100 Ω load)
Transmission error, typical0.08 % (of final value)
Electrical isolation Input/output/power supply
Rated insulation voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationSafe isolation in accordance with IEC/EN 61010-1
Supply
Supply voltage rangeloop-powered, no external supply necessary

Input data
Signal: Current
Number of inputs2
Configurable/programmableno
Max. voltage input signal< 30.5 V
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Input voltage limitation30.5 V
Voltage dissipation2.9 V (I = 20 mA)
Step response (10-90%)5 ms (500 Ω load)
Additional error, load-dependent0.022 % (of measured value / 100 Ω load)
Response currentapprox. 50 µA

Output data
Signal: Current
Number of outputs2
Configurable/programmableno
Max. voltage output signal27.5 V
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output≤ 1375 Ω (I = 20 mA)
Residual ripple< 10 mVrms(500 Ω load)

Connection data
Connection methodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm
Test socket
Max. diameter2.3 mm

Ex data
Ex installation (EPL)Gc
Div. 2

Dimensions
Dimensional drawing
Width12.5 mm
Height112.5 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)
Housing materialPA 6.6-FR

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (not assessed by UL)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude< 2000 m
Permissible humidity (operation)5 % ... 95 % (non-condensing)

Approvals
CE
CertificateCE-compliant
Noteand EN 61326-1
ATEX
Identification II 3 G Ex nA IIC T4 Gc X
UKCA Ex (UKEX)
Identification II 3 G Ex nA IIC T4 Gc X
CertificatePxCIF21UKEX2905278X
UL, USA/Canada
IdentificationUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Safety Integrity Level (SIL, IEC 61508)
Identification3
Certificate968/FSP 1200.01/21

EMC data
Electromagnetic compatibilityConformance with EMC directive
Noise immunityEN 61326-1
Noise emissionEN 61000-6-4

Standards and regulations
Electrical isolation2-way isolation

Mounting
Mounting typeDIN rail mounting

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.