View larger
MACX MCR-RTD-I-SP 1050201 PHOENIX CONTACT Temperature transducer, converts signals from resistance temperatu..
MACX MCR-RTD-I-SP
1050201
PHOENIX CONTACT
1 Pcs.
Automation > Temperature transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MACX MCR-RTD-I-SP 1050201 PHOENIX CONTACT Temperature transducer, converts signals from resistance temperature is an advanced signal converter built to translate resistance sensor inputs into standardized industrial currents. Process control engineers utilize these devices to ensure accurate and noise-free thermal data acquisition across extensive factory floors.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Measuring range (EF001836): -200 °C
- Analogue output 0 mA ... 20 mA (EF006808): Yes
- With switching output (EF005225): No
- EMC-version (EF001062): Yes
- Ambient temperature (EF002386): 70 °C
- Weight (EF000167): 0.15 kg
More info
▲Key Commercial Data
| Orderkey | 1050201 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 130 (C-5-2019) |
| GTIN | 4055626651293 |
| Weight per Piece (excluding packing) | 0.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
|---|---|
| Temperature measuring range | -200 °C ... 850 °C (Range depending on the sensor type) |
| Input signal range | 0 Ω ... 50 kΩ |
| Potentiometer resistance range | 0 Ω ... 50 kΩ |
| Cable resistance | ≤ 50 Ω per cable |
| Sensor input current | 10 µA ... 210 µA (up to 2 x 210 µA for 3-conductor) |
| Measuring range span | ≥ 50 K |
Output data
| Signal output | Current output |
|---|---|
| Configurable/programmable | Yes |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA (SIL) | |
| Max. current output signal | ≥ 21 mA |
| Load/output load current output | ≤ 600 Ω |
| Output ripple (current) | < 15 µAPP |
| Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Power dissipation | ≤ 0.76 W |
| Power consumption | ≤ 1 W |
General
| No. of channels | 1 |
|---|---|
| Transmission error, typical | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) |
| Temperature coefficient, typical | 0.01 %/K |
| Step response (0–99%) | typ. 1 s |
| ≤ 1.7 s | |
| Alignment zero | ± 5 % |
| Alignment span | ± 5 % |
| Status display | Green LED (supply voltage, PWR) |
| Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR) | |
| Red LED, flashing 1.2 Hz (service operation, ERR) | |
| Red LED, permanently on (module error, ERR) | |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Input/output/power supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/power supply |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II 3 G Ex ec ic IIC T4 Gc |
| IECEx | Ex ec ic IIC T4 Gc |
| SIL | 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 1 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 1 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 1 % |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II 3 G Ex ec ic IIC T4 Gc |
| IECEx | Ex ec ic IIC T4 Gc |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | B |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27210120 |
|---|---|
| eCl@ss 4.1 | 27210120 |
| eCl@ss 5.0 | 27210120 |
| eCl@ss 5.1 | 27210120 |
| eCl@ss 6.0 | 27210120 |
| eCl@ss 7.0 | 27210120 |
| eCl@ss 8.0 | 27200206 |
| eCl@ss 9.0 | 27210129 |
ETIM
| ETIM 2.0 | EC001446 |
|---|---|
| ETIM 3.0 | EC001446 |
| ETIM 4.0 | EC001446 |
| ETIM 5.0 | EC001446 |
| ETIM 6.0 | EC002919 |
| ETIM 7.0 | EC002919 |
UNSPSC
| UNSPSC 6.01 | 30211506 |
|---|---|
| UNSPSC 7.0901 | 39121008 |
| UNSPSC 11 | 39121008 |
| UNSPSC 12.01 | 39121008 |
| UNSPSC 13.2 | 41112105 |
| UNSPSC 18.0 | 41112105 |
| UNSPSC 19.0 | 41112105 |
| UNSPSC 20.0 | 41112105 |
| UNSPSC 21.0 | 41112105 |