View larger
MACX MCR-EX-TS-I-OLP-SP 2908661 PHOENIX CONTACT The output-loop-powered temperature transmitter transmits up..
MACX MCR-EX-TS-I-OLP-SP
2908661
PHOENIX CONTACT
1 Pcs.
Automation > Temperature transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact MACX MCR-EX-TS-I-OLP-SP is an output-loop-powered temperature transmitter utilized in hazardous environments to safely transmit industrial temperature signals from the field to control systems. Such loop-powered transmitters reduce wiring complexity while ensuring reliable signal conditioning and intrinsic safety protection in process automation setups.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Measuring range (EF001836): -250 °C
- Analogue output 0 mA ... 20 mA (EF006808): No
- Analogue output 4 mA ... 20 mA (EF006810): Yes
- Analogue output 0 V ... 2 V (EF009886): No
- Analogue output 0 V ... 5 V (EF009887): No
- Analogue output 0 V ... 10 V (EF006807): No
- Analogue output 2 V ... 10 V (EF009888): No
- With switching output (EF005225): No
- Modular version (EF001126): Yes
- Integrated configuration function (EF003064): No
- Ambient temperature (EF002386): 85 °C
- Weight (EF000167): 0.2057 kg
More info
▲Key Commercial Data
| Orderkey | 2908661 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 190 (C-5-2019) |
| GTIN | 4055626355436 |
| Weight per Piece (excluding packing) | 0.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| -40 °C ... 70 °C (SIL active) | |
| Ambient temperature (storage/transport) | -40 °C ... 100 °C |
| Maximum altitude | ≤ 4000 m (Above sea level) |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Degree of protection | IP20 (not assessed by UL) |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section solid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
General
| Step response (0–99%) | 0.8 s (TC) |
|---|---|
| Degree of pollution | 2 |
| Overvoltage category | II |
| Color | gray |
| Conformance | CE-compliant |
| ATEX | II 2 (1) G Ex ib [ia Ga] IIC T6...T4 Gb |
| IECEx | Ex ib [ia Ga] IIC T6...T4 Gb |
| UL, USA/Canada | UL 61010 Recognized |
| FM approval | Exia / Class I / Div. 1, 2 / Group ABCD |
| CSA | AIS / Class I / Div. 1 / ABCD |
Standards and Regulations
| Conformance | CE-compliant |
|---|---|
| ATEX | II 2 (1) G Ex ib [ia Ga] IIC T6...T4 Gb |
| IECEx | Ex ib [ia Ga] IIC T6...T4 Gb |
| UL, USA/Canada | UL 61010 Recognized |
| FM approval | Exia / Class I / Div. 1, 2 / Group ABCD |
| NI, Class I, Div. 2, Groups A, B, C, D | |
| CSA | AIS / Class I / Div. 1 / ABCD |
| NI / Class I / Div. 2 / ABCD T6/T5/T4 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |