View larger
MACX MCR-EX-SL-SD-21-25-LFD 2905669 PHOENIX CONTACT Solenoid driver
MACX MCR-EX-SL-SD-21-25-LFD
2905669
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact MACX MCR-EX-SL-SD-21-25-LFD solenoid driver safely operates and controls field devices installed in hazardous areas by providing necessary galvanic isolation and power limitation. Such interface modules are commonly utilized in process automation and industrial control environments to link safety-critical control systems with intrinsically safe valves and actuators. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 19.2 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
More info
▲Key Commercial Data
| Orderkey | 2905669 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 160 (C-5-2017) |
| GTIN | 4046356985079 |
| Weight per Piece (excluding packing) | 155.600 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Degree of protection | IP20 |
Output data
| Output characteristic curve: Output resistor | ≥ 641 Ω (Internal resistance Ri) |
|---|---|
| Response time | < 30 ms |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Power dissipation | < 0.8 W |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Connection method | Screw connection |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
General
| No. of channels | 1 |
|---|---|
| Status display | Green LED (supply voltage) |
| LED yellow (switching state) | |
| Red LED (line errors) | |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | green |
| Designation | Output/input, error message output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) | |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Output/supply, DIN rail connector |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) | |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Input/error message output/supply |
| Electrical isolation | 1.5 kV (50 Hz, 1 min., test voltage) |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3(1) G Ex nA [ia Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| UL, USA/Canada | UL 61010 Listed |
| SIL | 3 |
Safety data
| Max. internal inductance Li | negligible |
|---|---|
| Max. internal capacitance Ci | 11 nF |
| Max. output voltage Uo | 23.98 V |
| Max. output current Io | 37.4 mA |
| Max. output power Po | 224 mW |
| Group | IIC |
| Max. external inductivity Lo | 22 mH |
| Max. external capacity Co | 110 nF |
| Group | IIB |
| Max. external inductivity Lo | 100 mH |
| Max. external capacity Co | 910 nF |
| Group | IIA |
| Max. external inductivity Lo | 200 mH |
| Max. external capacity Co | 3330 nF |
| Safety-related maximum voltage Um | 253 V AC/DC |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3(1) G Ex nA [ia Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| UL, USA/Canada | UL 61010 Listed |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIB | |
| IIA |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |