View larger
MACX MCR-EX-SL-RPSS-2I-2I-SP 2924676 PHOENIX CONTACT Signal isolator
MACX MCR-EX-SL-RPSS-2I-2I-SP
2924676
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A MACX MCR-EX-SL-RPSS-2I-2I-SP 2924676 PHOENIX CONTACT Signal isolator is used in industrial installations to separate intrinsically safe circuits from non-intrinsically safe control environments. By breaking potential ground loops and filtering electrical noise, it helps maintain accurate sensor data transmission in demanding settings.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 19.2 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
More info
▲Key Commercial Data
| Orderkey | 2924676 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 142 (C-5-2017) |
| GTIN | 4046356665483 |
| Weight per Piece (excluding packing) | 163.800 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
| Signal input | Intrinsically safe |
|---|---|
| Current input signal | 4 mA ... 20 mA |
| Transmitter supply voltage | > 16 V (at 20 mA) |
| Underload/overload signal range | 0 mA ... 24 mA |
Output data
| Signal output | Current output |
|---|---|
| Current output signal | 4 mA ... 20 mA (active) |
| Transmission Behavior | 1:1 to input signal |
| Load/output load current output | ≤ 450 Ω (20 mA) |
| ≤ 375 Ω (24 mA) | |
| Output behavior in the event of an error | < 3.6 mA (In the event of cable break at the input (as per NE 43)) |
| > 22.5 mA (In the event of cable short circuit at the input (as per NE 43)) |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Max. current consumption | < 100 mA (24 V / 20 mA) |
| Power dissipation | < 1.4 W (at 24 V DC / 20 mA) |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
General
| No. of channels | 2 |
|---|---|
| Maximum transmission error | < 0.1 % (of final value) |
| Transmission error, typical | < 0.05 % (of final value) |
| Maximum temperature coefficient | < 0.01 %/K |
| Step response (10-90%) | < 1.3 ms (for 4 mA ... 20 mA step) |
| Status display | Green LED (supply voltage) |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | green |
| Designation | Input/output, power supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/power supply |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Output 1/output 2/ power supply |
| Electrical isolation | 1.5 kV (50 Hz, 1 min., test voltage) |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3(1) G Ex nA [ia Ga] IIC T4 Gc | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| SIL | 3 |
Safety data
| Max. output voltage Uo | 25.2 V |
|---|---|
| Max. output current Io | 93 mA |
| Max. output power Po | 587 mW |
| Group | IIC |
| Max. external inductivity Lo | 2 mH |
| Max. external capacity Co | 107 nF |
| Group | IIB |
| Max. external inductivity Lo | 4 mH |
| Max. external capacity Co | 820 nF |
| Safety-related maximum voltage Um | 253 V AC (125 V DC) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3(1) G Ex nA [ia Ga] IIC T4 Gc | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIB |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |