PHOENIX CONTACT MACX MCR-EX-SL-RPSS-2I-2I MACX MCR-EX-SL-RPSS-2I-2I 2865382 PHOENIX CONTACT Signal isolator View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MACX MCR-EX-SL-RPSS-2I-2I 2865382 PHOENIX CONTACT Signal isolator

MACX MCR-EX-SL-RPSS-2I-2I

2865382

PHOENIX CONTACT

1 Pcs.

Signal isolator Power signal conditioner for intrinsically safe power transducer, 2 channels; HART transparent. It powers intrinsically safe 2-conductor power transducers and transmits the 4 mA signal ... 20 mA from the Ex zone to the safe zone. 5-way galvanic separation, screw connection, up to SIL 3, PL.

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact MACX MCR-EX-SL-RPSS-2I-2I 2865382 PHOENIX CONTACT Signal isolator is an essential interface device deployed in electrical control panels to decouple, filter, and transmit analog process signals safely between field instruments and control systems. Units of this type protect sensitive control electronics from dangerous surges while maintaining high signal fidelity across complex automation networks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated supply voltage DC (EF007078): 19.2 V
  • Number of input ranges -60 mV ... +60 mV (EF006927): 0
  • Number of input ranges -100 mV ... +100 mV (EF006912): 0
  • Number of input ranges -300 mV ... +300 mV (EF006920): 0
  • Number of input ranges -500 mV ... +500 mV (EF006926): 0
  • Number of input ranges -1 V ... +1 V (EF006906): 0
  • Number of input ranges -2 V ... +2 V (EF006913): 0
  • Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
  • Number of input ranges -5 V ... +5 V (EF006923): 0
  • Number of input ranges -10 V ... +10 V (EF006909): 0
  • Number of input ranges -20 V ... +20 V (EF006917): 0
  • Number of input ranges 0 mV ... 60 mV (EF006905): 0
  • Number of input ranges 0 mV ... 100 mV (EF006893): 0
  • Number of input ranges 0 mV ... 200 mV (EF006898): 0
  • Number of input ranges 0 mV ... 300 mV (EF006901): 0
  • Number of input ranges 0 mV ... 500 mV (EF006904): 0

More info

▲

Key Commercial Data

Orderkey2865382
Packing unit1 pc
Catalog pagePage 142 (C-5-2017)
GTIN4046356160407
Weight per Piece (excluding packing)163.800 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width12.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Input data

Signal inputIntrinsically safe
Current input signal4 mA ... 20 mA
Transmitter supply voltage> 16 V (20 mA)
Underload/overload signal range0 mA ... 24 mA

Output data

Signal outputCurrent output
Current output signal4 mA ... 20 mA (active)
Transmission Behavior1:1 to input signal
Load/output load current output≤ 450 Ω (20 mA)
≤ 375 Ω (24 mA)
Output behavior in the event of an error< 3.6 mA (In the event of cable break at the input (as per NE 43))
> 22.5 mA (In the event of cable short circuit at the input (as per NE 43))

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption< 100 mA (24 V / 20 mA)
Power dissipation< 1.4 W (at 24 V DC / 20 mA)

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

No. of channels2
Maximum transmission error< 0.1 % (of final value)
Transmission error, typical< 0.05 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Step response (10-90%)< 1.3 ms (for 4 mA ... 20 mA step)
Status displayGreen LED (supply voltage)
Flammability rating according to UL 94V0
Degree of pollution2
Overvoltage categoryII
Electromagnetic compatibilityConformance with EMC directive
Interference emissionEN 61000-6-4
Housing materialPA 6.6-FR
Colorgreen
DesignationInput/output, power supply
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationInput/output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/power supply
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationOutput 1/output 2/ power supply
Electrical isolation1.5 kV (50 Hz, 1 min., test voltage)
ConformanceCE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
SIL3

Data communication (bypass)

HART functionYes
Protocols supportedHART

Safety data

Max. output voltage Uo25.2 V
Max. output current Io93 mA
Max. output power Po587 mW
GroupIIC
Max. external inductivity Lo2 mH
Max. external capacity Co107 nF
GroupIIB
Max. external inductivity Lo4 mH
Max. external capacity Co820 nF
Safety-related maximum voltage Um253 V AC (125 V DC)

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Flammability rating according to UL 94V0
ConformanceCE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCA
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board
GroupIIC
IIB

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.