Phoenix Contact MACX MCR-EX-AP-RPSS-I-I is an intrinsically safe repeater power supply designed to energize field transmitters while safely transmitting 4-20 mA signals across hazardous areas. These galvanic isolators provide vital explosion protection and signal transparency for process control applications in chemical and energy facilities.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General: Accuracy, typically specified as a percentage of the measuring span (20 mA) at U N , 23°C:
- General: Output behavior = input signal:
- Product type: Repeater power supplies
- Product family: MACX Analog
- No. of channels: 1
- No. of channels: 1
- Electrical isolation: 3-way isolation
- Signal transmission behavior: In = Out
- Temperature coefficient, typical: ≤ 0.05 % (10 K)
- Reverse polarity protection: yes
- Rated insulation voltage: 375 V PP
- Rated insulation voltage: 375 V PP
- Rated insulation voltage: 375 V PP
- Rated insulation voltage: 375 V PP
- Electrical isolation Output/supply Test voltage: 350 V (50 Hz, 60 s)
- Electrical isolation Output 1/output 2 Test voltage: 350 V (50 Hz, 60 s)
More info
▲| General | Accuracy, typically specified as a percentage of the measuring span (20 mA) at UN, 23°C |
| General | Installation conditions influence the ambient temperature. Please refer to the “Control cabinet installation instructions”. |
| General | Output behavior = input signal |
| Product type | Repeater power supplies |
| Product family | MACX Analog |
| No. of channels | 1 |
| No. of channels | 1 |
| Electrical isolation | 3-way isolation |
| Signal transmission behavior | In = Out |
| Temperature coefficient, typical | ≤ 0.05 % (10 K) |
| Reverse polarity protection | yes |
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 375 VPP |
| Electrical isolation Input/power supply IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 375 VPP |
| Electrical isolation Input/error message output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 375 VPP |
| Electrical isolation Input 1 / input 2 IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 375 VPP |
| Electrical isolation Output/supply | |
| Test voltage | 350 V (50 Hz, 60 s) |
| Electrical isolation Output 1/output 2 | |
| Test voltage | 350 V (50 Hz, 60 s) |
| Electrical isolation Output/supply/error message output | |
| Test voltage | 350 V (50 Hz, 60 s) |
| Supply | |
| Nominal supply voltage | 24 V DC |
| Supply voltage range | 18 V ... 31.2 V |
| Power dissipation | 2.2 W (RL250 Ω) |
| Power consumption | 2.7 W (20 mA) |
| Signal: Repeater power supply operation | |
| Description of the input | active and passive current input, intrinsically safe |
| Input signal | Current |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA (with HART) | |
| 0 mA ... 24 mA (Function area) | |
| Input resistance current input | ≤ 100 Ω (for mA sources) |
| Input current | ≤ 50 mA (for mA sources) |
| Short-circuit current | ≤ 35 mA |
| Line fault detection | < 3.6 mA (Line break) |
| > 20.5 mA (Short circuit) | |
| Non-load voltage | ≤ 26 V |
| Signal: Signal conditioner operation | |
| Description of the input | Passive current input, intrinsically safe |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA (with HART) | |
| 0 mA ... 24 mA (Function area) | |
| Input resistance current input | ≤ 100 Ω (for mA sources) |
| Input current | ≤ 50 mA |
| Short-circuit current | ≤ 35 mA |
| Line fault detection | < 3.6 mA (Line break) |
| > 20.5 mA (Short circuit) | |
| Non-load voltage | ≤ 26 V |
| Signal: Error message output | |
| Maximum switching voltage | 30 V |
| Max. switching current | 100 mA |
| Signal: Repeater power supply operation | |
| Output description | Current output (active) |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA (with HART) | |
| 0 mA ... 24 mA (Function area) | |
| Load | 0 Ω ... 600 Ω |
| 0 Ω ... 379 Ω (with internal 221 Ω resistance for HART) | |
| Output ripple (current) | ≤ 40 µA (effective) |
| Line fault detection | < 3.6 mA (Line break) |
| Signal: Signal conditioner operation | |
| Output description | Signal conditioner operation |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA (with HART) | |
| 0 mA ... 24 mA (Function area) | |
| Load | 0 Ω ... 600 Ω |
| 0 Ω ... 379 Ω (with internal 221 Ω resistance for HART) | |
| Output ripple (current) | ≤ 40 µA (effective) |
| Cross section AWG | (converted acc. to IEC) |
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Ex installation (EPL) | Gc |
| Ex i circuits (EPL) | Ga |
| Da | |
| Ma | |
| Safety data: Repeater power supply operation | |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Max. output voltage Uo | 27 V |
| Max. output current Io | 88 mA |
| Max. output power Po | 576 mW |
| Safety-related maximum voltage Um | 253 V AC |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 28 mH / 2330 nF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 17 mH / 705 nF |
| IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 2.3 mH / 90 nF |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 40 mH / 3750 nF |
| IIA (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 28 mH / 410 nF, 2 mH / 480 nF, 1 mH / 540 nF, 0.2 mH / 820 nF |
| IIB/IIIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 17 mH / 290 nF, 2 mH / 320 nF, 0.5 mH / 460 nF, 0.2 mH / 600 nF |
| IIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 2 mH / 42 nF, 1 mH / 56 nF, 0.5 mH / 72 nF, 0.2 mH / 90 nF |
| I (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 40 mH / 480 nF, 20 mH / 660 nF, 0.5 mH / 810 nF, 0.1 mH / 1200 nF |
| Safety data: Signal conditioner operation | |
| Note | With connection of power sources |
| Input voltage Ui | 30 V |
| Input current Ii | 100 mA |
| Input power Pi | limited internally |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Max. output voltage Uo | 4.1 V |
| Safety-related maximum voltage Um | 253 V AC |
| Data communication (bypass) | |
| Protocols supported | HART-transparent |
| Frequency measuring range | 0.5 kHz ... 10 kHz (bidirectional HART transmission) |
| Status display | Green LED (supply voltage) |
| Red LED (line errors) |
| Dimensional drawing | |
| Width | 17.5 mm |
| Height | 112.5 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Flammability rating according to UL 94 | V0 |
| Housing material | Polyamide (PA 6.6) |
| Ambient conditions | |
| Degree of protection | IP20 (Terminal blocks) |
| IP30 (Housing) | |
| Ambient temperature (operation) | -20 °C ... 70 °C (Stand-alone device: any mounting position) |
| -20 °C ... 55 °C (Group assembly: vertical DIN rail without circulating air) | |
| -20 °C ... 65 °C (Group assembly: vertical DIN rail with circulating air) | |
| -20 °C ... 60 °C (Group assembly: horizontal DIN rail without circulating air) | |
| -20 °C ... 65 °C (Group assembly: horizontal DIN rail with circulating air) | |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | ≤ 95 % (non-condensing) |
| ATEX | |
| Identification | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc | |
| I (M1) [Ex ia Ma] I | |
| IECEx | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA nC [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 3 |
| Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 |
| Electrical isolation | 3-way isolation |
| Mounting type | NS 35/15, NS 35/7,5 |
| Mounting position | vertical, horizontal |