View larger
MACX MCR-EX-AP-2SD-25-35-LP 1291176 PHOENIX CONTACT Ex i-Valve control block to activate Ex i magnetic valve..
MACX MCR-EX-AP-2SD-25-35-LP
1291176
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Activations of intrinsically safe magnetic valves in hazardous areas rely on a Phoenix Contact MACX MCR-EX-AP-2SD-25-35-LP solenoid driver. These specialized interface components securely transmit digital control signals from safe zones to field devices while maintaining galvanic isolation and limiting energy levels in explosion-prone environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Solenoid driver
- Product family: MACX Analog
- No. of channels: 2
- Electrical isolation: 4-way isolation
- Reverse polarity protection: yes
- Rated insulation voltage: 375 V PP
- Electrical isolation Output 1/output 2 Test voltage: 500 V (50 Hz, 60 s)
- Electrical isolation Input 1 / input 2 Test voltage: 350 V (50 Hz, 60 s)
- Supply Supply voltage range: loop-powered, no external supply necessary
- Power consumption: 0.5 W (+ (l A x 37 mW/mA))
- Signal: Digital Switching level "0" signal: 0 V ... 5 V
- Switching level "1" signal: 18 V ... 31.2 V
- Switching: Digital Output description: intrinsically safe
- Typical response time: ≤ 18 ms
- Typical turn-off time: ≤ 50 ms
More info
▲| General | Installation conditions influence the ambient temperature. Please refer to the “Control cabinet installation instructions”. |
| Product type | Solenoid driver |
| Product family | MACX Analog |
| No. of channels | 2 |
| No. of channels | 2 |
| Electrical isolation | 4-way isolation |
| Reverse polarity protection | yes |
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 375 VPP |
| Electrical isolation Output 1/output 2 | |
| Test voltage | 500 V (50 Hz, 60 s) |
| Electrical isolation Input 1 / input 2 | |
| Test voltage | 350 V (50 Hz, 60 s) |
| Supply | |
| Supply voltage range | loop-powered, no external supply necessary |
| Power consumption | 0.5 W (+ (lAx 37 mW/mA)) |
| Signal: Digital | |
| Switching level "0" signal | 0 V ... 5 V |
| Switching level "1" signal | 18 V ... 31.2 V |
| Switching: Digital | |
| Output description | intrinsically safe |
| Typical response time | ≤ 18 ms |
| Typical turn-off time | ≤ 50 ms |
| Switching frequency | ≤ 10 Hz |
| Cross section AWG | (converted acc. to IEC) |
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Ex installation (EPL) | Gc |
| Ex i circuits (EPL) | Ga |
| Da | |
| Ma | |
| Safety data: Highest values per output | |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | 1.1 nF |
| Max. output voltage Uo | 27.6 V |
| Max. output current Io | 110 mA (Ex ia) |
| 50 mA (Ex ib) | |
| Max. output power Po | 760 mW |
| Safety-related maximum voltage Um | 253 V AC |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 100 mH / 2.22 µF |
| IIB (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 9 mH / 667 nF |
| IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 1.2 mH / 85 nF |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 100 mH / 3.5 µF |
| Safety data: Highest values with two outputs connected in parallel | |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | 2.2 nF |
| Max. output voltage Uo | 27.6 V |
| Max. output current Io | 220 mA (Ex ia) |
| 100 mA (Ex ib) | |
| Max. output power Po | 1520 mW |
| Safety-related maximum voltage Um | 253 V AC |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 25 mH / 2.22 µF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 1.8 mH / 665 nF |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 40 mH / 3.5 µF |
| Status display | Yellow LED/per channel |
| Dimensional drawing | |
| Width | 17.5 mm |
| Height | 112.5 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Flammability rating according to UL 94 | V0 |
| Housing material | Polyamide (PA 6.6) |
| Ambient conditions | |
| Degree of protection | IP20 (Terminal blocks) |
| IP30 (Housing) | |
| Ambient temperature (operation) | -20 °C ... 70 °C (Stand-alone device: any mounting position) |
| -20 °C ... 50 °C (Group assembly: vertical DIN rail without circulating air) | |
| -20 °C ... 60 °C (Group assembly: vertical DIN rail with circulating air) | |
| -20 °C ... 60 °C (Group assembly: horizontal DIN rail without circulating air) | |
| -20 °C ... 65 °C (Group assembly: horizontal DIN rail with circulating air) | |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | ≤ 95 % (non-condensing) |
| ATEX | |
| Identification | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1) G Ex nA [ia Ga] IIC T4 Gc | |
| I (M1) [Ex ia Ma] I | |
| IECEx | |
| Identification | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 3 |
| Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 |
| Electrical isolation | 4-way isolation |
| Mounting type | NS 35/15, NS 35/7,5 |
| Mounting position | vertical, horizontal |