View larger
MACX MCR-EX-AP-2REL-2DI-LP 1292331 PHOENIX CONTACT The relay module separates the Ex i and non-Ex i control ..
MACX MCR-EX-AP-2REL-2DI-LP
1292331
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for low-voltage switch technology
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact manufactures the MACX MCR-EX-AP-2REL-2DI-LP relay module, designed to provide galvanic isolation between hazardous and safe areas in industrial installations. Such components safely separate control circuits and signal lines to protect sensitive automation equipment from overvoltage and fault conditions.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Type: Relay module
- Product Family: MACX Analog
- Number of channels: 2
- Galvanic Separation: 4-Way Separation
- Sizing Insulation Voltage: 375 V PP
- Galvanic Separation Input 1 / Input 2 Test voltage: 350 V (50 Hz, 60 sec)
- Feeding Supply voltage: Loop-powered, no external power required
- Dissipated Power: ≤ 0.4 W
- Control Ticket Description: Control input, not intrinsically safe
- Input Signal Voltage: 12 V ... 31.2 V (Switching Signal)
- Current absorption: < 25 mA (12 V)
- Commuting: Relay Description of the output: Intrinsic safety
- Contact Switching Type: 1 switched contact per channel
- Minimum Activation Voltage: 1 V (1 mA)
- Maximum Switching Voltage: 45 V DC (0.25 A)
More info
▲| General | The installation conditions influence the ambient temperature. Please note the operating instructions. |
| Product Type | Relay module |
| Product Family | MACX Analog |
| Number of channels | 2 |
| Number of channels | 2 |
| Galvanic Separation | 4-Way Separation |
| Galvanic Separation Input/Output IEC/EN 60079-11 | |
| Standards/Specifications | IEC/EN 60079-11 |
| Sizing Insulation Voltage | 375 VPP |
| Galvanic Separation Input 1 / Input 2 | |
| Test voltage | 350 V (50 Hz, 60 sec) |
| Feeding | |
| Supply voltage | Loop-powered, no external power required |
| Dissipated Power | ≤ 0.4 W |
| Control | |
| Ticket Description | Control input, not intrinsically safe |
| Input Signal Voltage | 12 V ... 31.2 V (Switching Signal) |
| Current absorption | < 25 mA (12 V) |
| < 17 mA (24 V ... 31.2 V) | |
| Commuting: Relay | |
| Description of the output | Intrinsic safety |
| Contact Switching Type | 1 switched contact per channel |
| Minimum Activation Voltage | 1 V (1 mA) |
| Maximum Switching Voltage | 45 V DC (0.25 A) |
| 30 V DC (4 A) | |
| 45 V AC (4 A, cos φ >0.7) | |
| Typical Connection Time | ≤ 10 ms |
| Typical Shutdown Time | ≤ 10 ms |
| Switching frequency | ≤ 15 Hz |
| AWG Conductor Section | (Converted according to IEC) |
| Connection type | Screw connection |
| Length to be de-insulated | 7 mm |
| Screw thread | M3 |
| Rigid conductor section | 0.2 mm² ... 2.5 mm² |
| Flexible conductor section | 0.2 mm² ... 2.5 mm² |
| AWG Conductor Section | 24 ... 14 |
| Ex Installation (EPL) | Gc |
| Intrinsically safe circuits (EPL) | Ga |
| Gives | |
| Ma | |
| Technical Safety Data | |
| Input voltage Ui | 45 V AC |
| Input Current Ii | 4 A |
| Internal inductance max. Li | despicable |
| Max. Internal Capacity Ci | despicable |
| Maximum safety voltage Um | 253 V AC |
| Technical Safety Data | |
| Input voltage Ui | 45 V DC |
| Input Current Ii | 0.25 A |
| Internal inductance max. Li | despicable |
| Max. Internal Capacity Ci | despicable |
| Maximum safety voltage Um | 253 V AC |
| Technical Safety Data | |
| Input voltage Ui | 30 V DC |
| Input Current Ii | 4 A |
| Internal inductance max. Li | despicable |
| Max. Internal Capacity Ci | despicable |
| Maximum safety voltage Um | 253 V AC |
| Dimension Scheme | |
| Width | 17.5 mm |
| Height | 112.5 mm |
| Depth | 113.7 mm |
| Depth NS 35/7.5 | 114.5 mm (fitted on DIN rail NS 35/7.5 according to EN 60715) |
| Flammability class according to UL 94 | V0 |
| Shell material | Polyamide (PA 6.6) |
| Environmental conditions | |
| Protection Index | IP20 (Terminals) |
| IP30 (Housing) | |
| Ambient Temperature (Service) | -20 °C ... 70 °C (Individual Equipment: Discretionary Mounting Position) |
| -20 °C ... 70 °C (Mounting in groups: vertical DIN rail without air circulation) | |
| -20 °C ... 70 °C (Mounting in groups: vertical DIN rail with air circulation) | |
| -20 °C ... 70 °C (Bracket mounting: horizontal DIN rail without air circulation) | |
| -20 °C ... 70 °C (Bracket mounting: horizontal DIN rail with air circulation) | |
| Ambient Temperature (Storage/Transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m |
| Permissible air humidity (service) | ≤ 95% (non-condensing) |
| ATEX | |
| Marked | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3(1) G Ex ec nC [ia Ga] IIC T4 Gc | |
| I (M1) [Ex ia Ma] I | |
| IECEx | |
| Marked | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex ec nC [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Safety Integrity Level (SIL, IEC 61508) | |
| Marked | 2 |
| Electromagnetic compatibility | Testing according to the following standards and requirements: EN 61326-1 for use in the industrial field, NAMUR NE 21 |
| Galvanic Separation | 4-Way Separation |
| Type of mounting | NS 35/15, NS 35/7.5 |
| Position for mounting | vertical, horizontal |