View larger
CTM 2X1-180DC-GS 2838636 PHOENIX CONTACT Surge protection plug
CTM 2X1-180DC-GS
2838636
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for industrial automation setups, the Phoenix Contact CTM 2X1-180DC-GS 2838636 PHOENIX CONTACT Surge protection plug shields sensitive measurement systems from destructive transient voltage surges. Pluggable transient protectors help maintain regulatory compliance and uninterrupted plant productivity.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 180 V
More info
▲Key Commercial Data
| Orderkey | 2838636 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 167 (C-4-2017) |
| GTIN | 4017918948382 |
| Weight per Piece (excluding packing) | 7.760 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | DIN VDE 0110-1 |
| IEC 60664-1 | |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Type | LSA-PLUS module |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 2.12 |
| Near-end crosstalk attenuation aN between adjacent articles | 70 dB (up to 1 MHz 100 Ω system) |
| 50 dB (up to 10 MHz 100 Ω system) | |
| 30 dB (up to 100 MHz, 100 Ω system) | |
| Transmission speed | 44 Mbps |
Protective circuit
| IEC test classification | A2 |
|---|---|
| B1 | |
| B2 | |
| B3 | |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| D2 | |
| VDE requirement class | A2 |
| B1 | |
| B2 | |
| B3 | |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| D2 | |
| Nominal voltage UN | 180 V DC |
| Maximum continuous voltage UC | ± 180 V DC |
| Rated current | 1.5 A (25 °C) |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs | 1 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Total discharge current Itotal(10/350) µs | 2.5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (in total) |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 200 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 800 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 800 V |
| Residual voltage at In(line-earth) | ≤ 70 V |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 28 V |
| Voltage protection level Up(line-earth) | ≤ 900 V (C2 - 10 kV/5 kA, spike) |
| ≤ 70 V (C2 - 10 kV/5 kA, static) | |
| ≤ 1 kV (C3 - 7.5 kV / 100 A, spike) | |
| ≤ 30 V (C3 - 7.5 kV / 100 A, static) | |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, asym. | 0.1 dB (≤ 10 MHz) |
| 0.2 dB (≤ 60 MHz) | |
| 0.5 dB (≤ 100 MHz) | |
| Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system | > 100 MHz |
| Capacity (line-earth) | 5 pF (f=1 MHz / VR= 0 V) |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 4 kV/2 kA |
| C3 - 100 A | |
| B2 - 4 kV/100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
|---|---|
| Connection method IN | COMTRAB plug-in system |
| Connection method OUT | COMTRAB plug-in system |
| Connection technology | LSA-PLUS |