View larger
CTM 2X1- 60DC 2838542 PHOENIX CONTACT Surge protection plug
CTM 2X1-60DC
2838542
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Industrial measurement setups utilize the Phoenix Contact CTM 2X1-60DC 2838542 PHOENIX CONTACT Surge protection plug to prevent transient overvoltages from damaging sensitive loop-powered equipment. Pluggable transient suppressors are essential for maintaining the integrity of automation data lines and field transmitters.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 60 V
More info
▲Key Commercial Data
| Orderkey | 2838542 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 119 (C-4-2017) |
| GTIN | 4017918819576 |
| Weight per Piece (excluding packing) | 10.580 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 75 °C |
|---|---|
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Type | LSA-PLUS module |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 60 V DC |
| Maximum continuous voltage UC | 60 V DC |
| 50 V AC | |
| Rated current | 380 mA AC (25 °C) |
| 150 mA DC (25 °C) | |
| Operating effective current ICat UC | ≤ 70 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 1 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Total discharge current Itotal(10/350) µs | 2.5 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 160 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 160 V |
| Residual voltage at In(line-earth) | ≤ 95 V |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 16 V |
| Voltage protection level Up(line-earth) | ≤ 240 V (C2 - 10 kV / 5 kA) |
| ≤ 150 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 85 V (C2 - 10 kV / 5 kA) |
| ≤ 16 V (C3 - 100 A) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 500 kHz / 100 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system | typ. 2 MHz |
| Capacity (line-earth) | typ. 1 nF |
| Resistance in series | 3.3 Ω 20 % |
| Surge protection fault message | none |
| Impulse durability (line-earth) | B2 - 4 kV/100 A |
| C2 - 10 kV/5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
|---|---|
| Connection method IN | COMTRAB plug-in system |
| Connection method OUT | COMTRAB plug-in system |
| Connection technology | LSA-PLUS |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |