View larger
CTM 2X1- 12DC 2838584 PHOENIX CONTACT Surge protection plug
CTM 2X1-12DC
2838584
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact CTM 2X1- 12DC 2838584 surge protection plug is utilized in electrical and control engineering to prevent voltage surges from disrupting low-voltage communication lines. These modular protective plugs absorb and divert harmful electrical impulses, extending the operational life of connected instrumentation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 12 V
More info
▲Key Commercial Data
| Orderkey | 2838584 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 119 (C-4-2017) |
| GTIN | 4017918819606 |
| Weight per Piece (excluding packing) | 10.560 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | DIN VDE 0110-1 |
| IEC 60664-1 | |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Type | LSA-PLUS module |
| Number of positions | 2 |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | ± 15 V DC |
| 10 V AC | |
| Rated current | 380 mA AC (25 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 1 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Total discharge current Itotal(10/350) µs | 2.5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (in total) |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 28 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 22 V |
| Residual voltage at In(line-earth) | ≤ 32 V |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 18 V |
| Voltage protection level Up(line-earth) | ≤ 60 V (C2 - 10 kV/5 kA, spike) |
| ≤ 30 V (C3 - 7.5 kV / 100 A, spike) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, sym. | |
| Input attenuation aE, asym. | 0.3 dB (≤ 400 kHz) |
| Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system | 1.5 MHz |
| Capacity (line-earth) | 1.5 nF (f=1 MHz / VR= 0 V) |
| Resistance in series | 3.3 Ω 10 % |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 4 kV/2 kA |
| C3 - 100 A | |
| B2 - 4 kV/100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
|---|---|
| Connection method IN | COMTRAB plug-in system |
| Connection method OUT | COMTRAB plug-in system |
| Connection technology | LSA-PLUS |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |