PHOENIX CONTACT CTM 1X2-60DC CTM 1X2- 60DC 2838568 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CTM 1X2- 60DC 2838568 PHOENIX CONTACT Surge protection plug

CTM 1X2-60DC

2838568

PHOENIX CONTACT

1 Pcs.

Surge protection plug LSA-PLUS (COMTRAB CTM) plug-in protection with 2-wire circuit protection for signal circuits without ground potential. Rated voltage: 60 V DC

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact CTM 1X2-60DC surge protection plug is engineered to provide targeted transient suppression for telecommunications and measurement circuits. These compact plug-in modules safeguard sensitive field instruments against electrical disturbances and surges caused by switching operations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Nominal voltage DC (EF008799): 60 V

More info

▲

Key Commercial Data

Orderkey2838568
Packing unit10 pc
Catalog pagePage 102 (C-4-2017)
GTIN4017918819736
Weight per Piece (excluding packing)10.080 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height21 mm
Width9.4 mm
Depth52.4 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 75 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Overvoltage categoryII
Degree of pollution2
Mounting typeOn CT-TERMIBLOCK and LSA-PLUS disconnect strip
TypeLSA-PLUS module
Direction of actionLine-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
Nominal voltage UN60 V DC
Maximum continuous voltage UC60 V DC
50 V AC
Rated current380 mA AC (25 °C)
150 mA DC (25 °C)
Operating effective current ICat UC≤ 70 µA
Residual current IPE≤ 2 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)1 kA
Total discharge current Itotal(8/20) µs10 kA
Total discharge current Itotal(10/350) µs2.5 kA
Nominal pulse current Ian (10/1000) µs (line-line)100 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 160 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 700 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 700 V
Residual voltage at In(line-line)≤ 95 V
Residual voltage at In(line-earth)≤ 60 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 35 V
Residual voltage with Ian (10/1000) µs (line-earth)≤ 12 V
Voltage protection level Up(line-line)≤ 200 V (C2 - 10 kV / 5 kA)
≤ 160 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 700 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 100 A)
Voltage protection level Upstatic (line-line)≤ 95 V (C2 - 10 kV / 5 kA)
≤ 35 V (C3 - 100 A)
Voltage protection level Upstatic (line-earth)≤ 90 V (C2 - 10 kV / 5 kA)
≤ 12 V (C3 - 100 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 500 kHz / 100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 2 MHz
Capacity (line-line)typ. 1.2 nF
Resistance in series3.3 Ω 20 %
Surge protection fault messagenone
Impulse durability (line-line)B2 - 4 kV/100 A
C2 - 10 kV/5 kA
C3 - 100 A
Impulse durability (line-earth)B2 - 4 kV/100 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1 kA
Alternating current carrying capacity (line-earth)5 A - 1 s

Connection data

Connection methodcan be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection method INCOMTRAB plug-in system
Connection method OUTCOMTRAB plug-in system
Connection technologyLSA-PLUS

Connection, equipotential bonding

Connection methodSpring contact

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.