PHOENIX CONTACT CTM 1X2-24DC CTM 1X2- 24DC 2838513 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CTM 1X2- 24DC 2838513 PHOENIX CONTACT Surge protection plug

CTM 1X2-24DC

2838513

PHOENIX CONTACT

1 Pcs.

Surge protection plug LSA-PLUS (COMTRAB CTM) plug-in protection with 2-wire circuit protection for signal circuits without ground potential. Rated voltage: 24 V DC

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact CTM 1X2- 24DC surge protection plug delivers dependable defense for telecommunication and signal wiring against sudden electrical surges. This compact component style is commonly implemented in dense control architectures where space-saving surge suppression is critical. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Nominal voltage DC (EF008799): 24 V

More info

▲

Key Commercial Data

Orderkey2838513
Packing unit10 pc
Catalog pagePage 102 (C-4-2017)
GTIN4017918819545
Weight per Piece (excluding packing)10.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height21 mm
Width9.5 mm
Depth53.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 75 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesDIN VDE 0110-1
IEC 60664-1
Overvoltage categoryII
Degree of pollution2
Mounting typeOn CT-TERMIBLOCK and LSA-PLUS disconnect strip
TypeLSA-PLUS module
Number of positions2
Direction of actionLine-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
VDE requirement classB2
C1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC± 30 V DC
21 V AC
Rated current380 mA AC (25 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 2 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)1 kA
Total discharge current Itotal(8/20) µs10 kA
Total discharge current Itotal(10/350) µs2.5 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA (in total)
Nominal pulse current Ian (10/1000) µs (line-line)100 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 70 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 700 V
Output voltage limitation at 1 kV/µs (line-line) static≤ 70 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 700 V
Residual voltage at In(line-line)≤ 45 V
Residual voltage at In(line-earth)≤ 60 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 25 V
Residual voltage with Ian (10/1000) µs (line-earth)≤ 12 V
Voltage protection level Up(line-line)≤ 70 V (C2 - 10 kV / 5 kA)
≤ 45 V (C3, 7.5 kV/100 A)
Voltage protection level Up(line-earth)≤ 700 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3, 7.5 kV/100 A)
Voltage protection level Upstatic (line-line)≤ 45 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3, 7.5 kV/100 A)
Voltage protection level Upstatic (line-earth)≤ 60 V (C2 - 10 kV / 5 kA)
≤ 12 V (C3, 7.5 kV/100 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.0.3 dB (≤ 600 kHz)
Input attenuation aE, asym.
Cut-off frequency fg (3 dB), sym. in 100 Ohm system2.7 MHz
Capacity (line-line)1.2 nF (f=1 MHz / VR= 0 V)
Resistance in series3.3 Ω 10 %
Surge protection fault messagenone
Impulse durability (line-line)C2 - 4 kV / 2 kA
C3 - 100 A
B2 - 4 kV/100 A
Impulse durability (line-earth)C2 - 4 kV/2 kA
C3 - 100 A
B2 - 4 kV/100 A
D1 - 1 kA
Alternating current carrying capacity (line-earth)5 A - 1 s

Connection data

Connection methodcan be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection method INCOMTRAB plug-in system
Connection method OUTCOMTRAB plug-in system
Connection technologyLSA-PLUS

Connection, equipotential bonding

Connection methodSpring contact

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2000

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.