PHOENIX CONTACT PT 1,5/S-TWIN-MT BU PT 1,5/S-TWIN-MT BU 3210312 PHOENIX CONTACT Knife disconnect terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT 1,5/S-TWIN-MT BU 3210312 PHOENIX CONTACT Knife disconnect terminal block

PT 1,5/S-TWIN-MT BU

3210312

PHOENIX CONTACT

50 Pcs.

Knife disconnect terminal block Blade interruptible terminal block, nominal voltage: 400 V, nominal current: 10 A, 1st floor, connection type: Push-in connection, Dimensioning cross-section: 1.5 mm², cross-section: 0.14 mm² - 1.5 mm², mounting: NS 35/7.5, NS 35/15, colour: blue

Automation > (Knife) disconnect terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Built for space-constrained control panels, the Phoenix Contact PT 1,5/S-TWIN-MT BU knife disconnect terminal block provides high-density signal routing with integrated disconnection blades. Twin terminal designs allow multiple conductors to share a common potential while maintaining individual line interruption.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Connectable conductor cross section solid-core (EF007337): 0.14 mm²
  • Rated current In (EF008250): 10 A
  • Rated voltage (EF000228): 400 V
  • Number of clamp positions per level (EF002660): 3
  • Internally connected stages (EF002661): Yes
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 3.5 mm
  • Height (EF000040): 67.8 mm
  • Depth (EF000049): 30.5 mm
  • Closing plate required (EF002525): Yes
  • Colour (EF000007): Blue
  • With integrated test socket (EF002547): No

More info

▲

Key Commercial Data

Orderkey3210312
Packing unit50 pc
Minimum order quantity50 pc
NoteMade to Order (non-returnable)
Catalog pagePage 40 (C-1-2017)
GTIN4046356905596
Weight per Piece (excluding packing)5.470 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of levels1
Number of connections3
Potentials1
Nominal cross section1.5 mm²
Colorblue
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.56 W
Maximum load current10 A
Nominal current IN10 A
Nominal voltage UN400 V
Open side panelYes
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width3.5 mm
End cover width0.8 mm
Length67.8 mm
Height30.5 mm
Height NS 35/7,532 mm
Height NS 35/1539.5 mm

Connection data

Connection methodPush-in connection
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible26
Max. AWG conductor cross section, flexible14
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.1 mm² Using the AI-S 1-8 TQ ferrule, Order No. 1200293, is recommended
Internal cylindrical gageA1 / B1

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.