Spark gap Separation arc unloader for the Ex zone with plastic enclosure and threaded screw for M10 connection. For the indirect connection/grounding of separate system parts depending on the operation in the event of lightning strikes.

Automation > Spark gap for overvoltage protection
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact FLT-ISG-100-EX 2905579 PHOENIX CONTACT Spark gap functions as an isolating spark gap designed to safely bypass galvanically separated conductive installation parts during lightning strikes or high-voltage surges. Devices of this type protect industrial plant components and personnel in hazardous atmospheres.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Voltage (EF002355): 250 kV

More info

▲

Key Commercial Data

Orderkey2905579
Packing unit1 pc
Catalog pagePage 78 (C-4-2017)
GTIN4055626002446
Weight per Piece (excluding packing)285.400 g
Custom tariff number73269098
Country of originDE (Germany)

Dimensions

Length100 mm +2 mm
Diameter housing45.50 mm

Ambient conditions

Degree of protectionIP67 (according to IEC 60529)
Ambient temperature (operation)-20 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 60 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)95 % (According to DIN ISO 60068-2-30 method 1)

General

Mounting typeScrew mounting
Colortraffic grey A RAL 7042
TypeScrew-on module
Surge protection fault messagenone

Additional descriptions

NoteConnection: screw (DIN 933), M10x25, wrench size: 17 mm, spring washer (DIN 7980), size: 10

Protective circuit

Nominal discharge current In(8/20) µs100 kA
Maximum discharge current Imax(8/20) µs (Shield-Earth)100 kA
Alternating voltage response Uaw≤ 0.5 kV
Rated power-frequency withstand voltage UwAC250 V AC
Rated DC withstand voltage UwDC354 V DC
Rated impulse sparkover voltage Ur imp≤ 1.25 kV
Rated alternating discharge current500 A / 0.2 s (at 50/60 Hz, max. discharge current in the event of external voltage influence at the installation location)
Response time tA≤ 100 ns

Connection data

Connection nameFlange
Connection methodConnection bolts
Screw threadM10

Standards and Regulations

Standards/regulationsIEC 62561-3 2012
EN 62561-3 2012

Conformity / approvals

ATEX II 2 G Ex d IIC T6 Gb
 II 2 D Ex tb IIIC T80 °C Db IP 66/67
IECExEx d IIC T6 Gb
Ex tb IIIC T80 °C Db IP66/67

Environmental Product Compliance