View larger
PS 6-DI-SD 3246856 PHOENIX CONTACT Isolating plugs
PS 6-DI-SD
3246856
PHOENIX CONTACT
50 Pcs.
Automation > Accessories/spare parts for terminals
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An isolating plug by Phoenix Contact, specifically the PS 6-DI-SD model, functions as a specialized disconnect terminal accessory used within industrial control cabinets to safely interrupt circuits during testing and maintenance procedures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 3246856
- Packing unit: 50 pc
- Minimum order quantity: 50 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 491 (C-1-2017)
- GTIN: 4046356915182
- Weight per Piece (excluding packing): 4.570 g
- Custom tariff number: 85366990
- Country of origin: PL (Poland)
- Number of positions: 1
- Color: gray
- Insulating material: PA
- Flammability rating according to UL 94: V0
- Degree of pollution: 3
- Result of bending test: Test passed
- Bending test rotation speed: 10 rpm
More info
▲Key Commercial Data
| Orderkey | 3246856 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 491 (C-1-2017) |
| GTIN | 4046356915182 |
| Weight per Piece (excluding packing) | 4.570 g |
| Custom tariff number | 85366990 |
| Country of origin | PL (Poland) |
General
| Number of positions | 1 |
|---|---|
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 3 |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.5 mm² / 0.3 kg |
| 2.5 mm² / 0.7 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.5 mm² |
| Tractive force setpoint | 20 N |
| Conductor cross section tensile test | 2.5 mm² |
| Tractive force setpoint | 50 N |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Standards and Regulations
| Flammability rating according to UL 94 | V0 |
|---|---|
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |