View larger
IOL MA8 EIP DI8 1072839 PHOENIX CONTACT Eight-channel IO-Link master provides convenient configuration of IO..
IOL MA8 EIP DI8
1072839
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact IOL MA8 EIP DI8 1072839 Eight-channel IO-Link master provides convenient configuration of IO operates as a decentralized network node that links smart sensors and actuators to higher-level automation systems. IO-Link masters streamline machine diagnostics and parameter management by gathering device data and transmitting it across industrial fieldbuses.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for EtherNet/IP (EF007521): No
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- IO link master (EF007298): Yes
- System accessory (EF004118): Yes
- Degree of protection (IP) (EF005474): IP20
- With potential separation (EF003272): No
- Suitable for rail mounting (EF003972): Yes
- Wall mounting/direct mounting (EF007020): No
- Front built-in possible (EF007016): No
- Rack-assembly possible (EF007018): No
- Suitable for safety functions (EF001597): No
- Appendant operation agent (Ex ia) (EF004141): No
- Appendant operation agent (Ex ib) (EF004142): No
More info
▲Key Commercial Data
| Orderkey | 1072839 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 163 (C-6-2019) |
| GTIN | 4055626766904 |
| Weight per Piece (excluding packing) | 0.010 g |
| Custom tariff number | 85176200 |
| Country of origin | US (United States) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % |
| Permissible humidity (storage/transport) | 10 % ... 95 % |
| Degree of protection | IP20 |
Connection data
| Connection method | Push-in technology |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 10 mm |
Interfaces
| Designation | EtherNet/IP™ |
|---|---|
| No. of channels | 2 |
| Connection method | RJ45 socket |
| Transmission speed | 10/100 Mbps (with auto negotiation) |
| Transmission physics | Ethernet in RJ45 twisted pair |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | IEC 61131-2 type 1 |
| Connection method | Push-in / plug connection |
| Connection technology | 3-wire |
| Number of inputs | 8 |
| Protective circuit | Overload protection |
| Short-circuit protection for the sensor supply | |
| Nominal input voltage UIN | 24 V DC |
| Nominal input current at UIN | typ. 3.5 mA |
| Input voltage range "0" signal | 0 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Input frequency | 0.5 kHz |
| Input name | Digital inputs |
| Description of the input | IO-Link ports in digital input (DI) mode |
| Connection method | Push-in / plug connection |
| Connection technology | 3-wire |
| Number of inputs | max. 8 (EN 61131-2 types 1 and 3) |
| Nominal input voltage UIN | 24 V DC |
| Input voltage range "0" signal | 8 V DC ... 11.5 V DC (for C/Q pin) |
| Input voltage range "1" signal | 10.5 V DC ... 13 V DC |
| Sensor current per channel | max. 200 mA (from L+/L-) |
| Total sensor current | max. 1.6 A (from L+/L-) |
| Type of protection | Overload protection |
| Short-circuit protection for the sensor supply |
IO-Link inputs
| Number of ports | 8 |
|---|---|
| Connection method | Push-in / plug connection |
| Connection technology | 3-wire |
| Description of the input | Digital inputs (DI) |
| Connection method | Push-in / plug connection |
| Nominal input voltage UIN | 24 V DC |
| Input voltage range "0" signal | 5.2 V DC ... 6.4 V DC |
| Input voltage range "1" signal | 6.8 V DC ... 8 V DC |
| Nominal input current | typ. 3.5 mA |
| Sensor current per channel | max. 200 mA (from L+/L-) |
| Total sensor current | max. 1.6 A (from L+/L-) |
| Type of protection | Overload protection |
| Short-circuit protection for the sensor supply |
Digital outputs
| Maximum output current per channel | 200 mA |
|---|---|
| Output description | IO-Link ports in digital output (DO) mode |
| Connection method | Push-in / plug connection |
| Connection technology | 3-wire |
| Number of outputs | max. 8 |
| Nominal output voltage | 24 V DC |
| Maximum output current per channel | 200 mA |
| Maximum output current per device | 1.6 A |
| Nominal load, ohmic | 4.8 W (120 Ω, at nominal load) |
| Output voltage when switched off | max. 1 V |
| Output current when switched off | max. 400 µA |
| Type of protection | Overload protection |
| Short-circuit protection | |
| Behavior with overload | Shutdown with automatic restart |
Supply of the IO-Link ports
| Nominal voltage for I/O supply | 24 V DC |
|---|---|
| Nominal current for every IO-Link port | max. 200 mA (at C/Q) |
| max. 200 mA (at L+/L-) | |
| Type of protection | Overload protection |
| Permissible cable length | < 20 m |
Electrical isolation
| Test section | 24 V supply/Ethernet 500 V AC 50 Hz 1 min. |
|---|---|
| 24 V supply (US) / FE 500 V AC 50 Hz 1 min. | |
| Ethernet/FE 500 V AC 50 Hz 1 min. | |
| Ethernet/Ethernet 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 1g |
|---|---|
| 15g | |
| pass |