View larger
DEK-TR/INV 2964319 PHOENIX CONTACT Switching amplifier
DEK-TR/INV
2964319
PHOENIX CONTACT
1 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
DEK-TR/INV by Phoenix Contact is a switching amplifier used in automation installations to condition, amplify, or invert digital control signals. These interface components ensure proper logic level compatibility between divergent automation hardware platforms. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- With LED indication (EF005950): No
More info
▲Key Commercial Data
| Orderkey | 2964319 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 453 (C-5-2017) |
| GTIN | 4017918176068 |
| Weight per Piece (excluding packing) | 19.900 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
General
| Supply voltage range | 20 V DC ... 30 V DC (UV) |
|---|---|
| Continuous current | 200 mA |
| Residual voltage drop | < 1 V |
| Leakage current | < 1 mA |
| Max. transmission frequency | 15 kHz |
NPN input/PNP output
| Switch-on threshold | < 5 V (at UV= 24 V; < (UV- 19 V)) |
|---|---|
| Switch-off threshold | > 15 V (at UV= 24 V; > (UV- 9 V)) |
| Min. limit values | -2 V |
| Max. limit values | 26 V (at UV= 24 V; UV+ 2 V) |
PNP input/NPN output
| Switch-on threshold | > 19 V |
|---|---|
| Switch-off threshold | < 9 V |
| Min. limit values | -2 V |
| Max. limit values | 26 V (at UV= 24 V; UV+ 2 V) |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
General
| Type of note | Note on application |
|---|---|
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |