View larger
PSM-ME-RS232/RS485-P 2744416 PHOENIX CONTACT Interface converter
PSM-ME-RS232/RS485-P
2744416
PHOENIX CONTACT
1 Pcs.
Automation > PLC communication module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An interface converter from Phoenix Contact, specifically part PSM-ME-RS232/RS485-P, conditions and converts serial communication signals to ensure reliable data exchange over extended distances in industrial systems. These devices protect sensitive electronics while maintaining signal integrity across harsh electrical environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Note on application Note on application: Only for industrial use
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China.
- Product type: Interface converter
- Application: RS-232
- MTTF: 1654 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
- Data management status Article revision: 22
- Insulation characteristics Pollution degree: 2
- Electrical isolation: VCC // V.24 (RS-232) // RS-485
- Maximum power dissipation for nominal condition: 2.04 W
- Test voltage data interface/power supply: 1.5 kV AC
- Test voltage data interfaces: 1.5 kV AC
- Supply Supply voltage range: 18 V AC/DC ... 30 V AC/DC (via pluggable COMBICON screw terminal block)
- Nominal supply voltage: 24 V AC/DC
- Typical current consumption: 85 mA (24 V DC)
- Max. current consumption: 100 mA
More info
▲| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Product type | Interface converter |
| Application | RS-232 |
| RS-422 | |
| RS-485 | |
| MTTF | 1654 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| 746 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
| 310 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) | |
| MTBF | 10 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
| Data management status | |
| Article revision | 22 |
| Insulation characteristics | |
| Pollution degree | 2 |
| Electrical isolation | VCC // V.24 (RS-232) // RS-485 |
| Maximum power dissipation for nominal condition | 2.04 W |
| Test voltage data interface/power supply | 1.5 kV AC |
| 1.5 kV AC | |
| Test voltage data interfaces | 1.5 kV AC |
| Supply | |
| Supply voltage range | 18 V AC/DC ... 30 V AC/DC (via pluggable COMBICON screw terminal block) |
| Nominal supply voltage | 24 V AC/DC |
| Typical current consumption | 85 mA (24 V DC) |
| Max. current consumption | 100 mA |
| Supply | |
| Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section, flexible [AWG] | 24 ... 12 |
| Tightening torque | 0.56 Nm ... 0.79 Nm |
| Interface | RS-232/-485 |
| Bit distortion | ≤ 5 % |
| Bit delay | ≤ 2.5 µs |
| Signal | Modbus |
| Transmission channels | 2 (1/1), RxD, TxD, full duplex |
| Data: V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN 66259-1 | |
| Serial transmission speed | 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 31.25; 38.4; 57.6; 75; 93.75; 115.2 kbps |
| Connection method | D-SUB 9 plug |
| Pin assignment | DTE/DCE switchover via switch |
| Transmission length | 15 m (shielded twisted pair) |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Max. AWG conductor cross section, flexible | 12 |
| Min. AWG conductor cross section, flexible | 24 |
| Protocols supported | transparent protocol |
| Data: RS-422 interface in acc. with ITU-T V.11, EIA/TIA-422, DIN 66348-1 | |
| Serial transmission speed | 1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 75; 93.75; 115.2 kbps |
| Connection method | Pluggable screw connection |
| Transmission length | 1200 m (shielded twisted pair) |
| Termination resistor | 390 Ω |
| 150 Ω | |
| 390 Ω (Can be connected) | |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Max. AWG conductor cross section, flexible | 13 |
| Min. AWG conductor cross section, flexible | 24 |
| Protocols supported | transparent protocol |
| Data: RS-485 interface in acc. with EIA/TIA-485, DIN 66259-1 | |
| Serial transmission speed | 1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 75; 93.75; 115.2 kbps |
| Connection method | Pluggable screw connection |
| Transmission length | 1200 m (shielded twisted pair) |
| Termination resistor | 390 Ω |
| 150 Ω | |
| 390 Ω (Can be connected) | |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Max. AWG conductor cross section, flexible | 14 |
| Min. AWG conductor cross section, flexible | 24 |
| Data direction switching | Automatic control or via RTS/CTS |
| Protocols supported | transparent protocol |
| Dimensional drawing | |
| Width | 22.5 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
| Color (Housing) | green (RAL 6021) |
| Material (Housing) | PA 6.6-FR |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| CE | |
| Certificate | CE-compliant |
| ATEX | |
| Identification | II 3 G Ex nA IIC T4 Gc |
| Certificate | IBExU16ATEXB004 X |
| Note | Please follow the special installation instructions in the documentation! |
| IECEx | |
| Identification | Ex nA IIC T4 Gc |
| Certificate | IECEx IBE 15.0034X |
| UL, USA/Canada | |
| Identification | 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| Class I, Zone 2, AEx nA IIC T4 | |
| Class I, Zone 2, Ex nA IIC T4 Gc X | |
| KC approval for South Korea | |
| Certificate | MSIP-REI-PCK-ME2744416 |
| Corrosive gas test | |
| Identification | ISA-S71.04-1985 G3 Harsh Group A |
| Shipbuilding | |
| Identification | DNV GL |
| DNV GL data | |
| Temperature | B |
| Humidity | A |
| Vibration | A |
| EMC | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise immunity | EN 61000-6-2:2005 |
| Noise emission | EN 61000-6-4 |
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 |
| Electrostatic discharge | |
| Contact discharge | ± 6 kV (Test Level 3) |
| Discharge in air | ± 8 kV (Test Level 3) |
| Comments | Criterion B |
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 |
| Electromagnetic HF field | |
| Frequency range | 26 MHz ... 3 GHz (Test Level 3) |
| Field intensity | 10 V/m |
| Comments | Criterion A |
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 |
| Fast transients (burst) | |
| Input | ± 2.2 kV (Test Level 3) |
| Signal | ± 2.2 kV (Test Level 3) |
| Comments | Criterion B |
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 |
| Surge current load (surge) | |
| Input | ± 0.5 kV (DC supply) |
| Signal | ± 1 kV (Data line, asymmetrical) |
| Comments | Criterion B |
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 |
| Conducted interference | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Comments | Criterion A |
| Voltage | 10 V |
| Emitted interference | |
| Standards/regulations | EN 55011 |
| Comments | Class A, industrial applications |
| Criteria | |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Mounting type | DIN rail mounting |