View larger
PSM-ME-RS232/RS232-P 2744461 PHOENIX CONTACT Interface converter
PSM-ME-RS232/RS232-P
2744461
PHOENIX CONTACT
1 Pcs.
Automation > PLC communication module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An interface converter such as the Phoenix Contact PSM-ME-RS232/RS232-P is utilized in industrial environments to condition, isolate, or translate serial signals between different automation equipment. This hardware helps eliminate ground loops, protects sensitive ports from electrical surges, and ensures reliable data transmission across complex factory floors. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for TCP/IP (EF003050): No
- Supporting protocol for PROFIBUS (EF003052): No
- Supporting protocol for CAN (EF003053): No
- Supporting protocol for INTERBUS (EF003054): No
More info
▲Key Commercial Data
| Orderkey | 2744461 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 322 (C-6-2017) |
| GTIN | 4017918188795 |
| Weight per Piece (excluding packing) | 123.180 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | 0 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Altitude | 5000 m (For restrictions see manufacturer's declaration) |
| Degree of protection | IP20 |
| Noise immunity | EN 61000-6-2:2005 |
General
| Transmission channels | 4 (2/2), RxD, TxD, RTS, CTS; full duplex |
|---|---|
| Bit delay | < 3 µs |
| Bit distortion | < 5 % |
| Electrical isolation | VCC // V.24 (RS-232) (A) // V.24 (RS-232) (B) |
| Test voltage data interfaces | 2 kV AC |
| Test voltage data interface/power supply | 2 kV AC |
| 2 kVrms(50 Hz, 1 min.) | |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise emission | EN 61000-6-3 |
| Net weight | 123.18 g |
| Housing material | PA |
| Color | green |
| MTBF | 2263 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| 438 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | |
| Conformance | CE-compliant |
| UL, USA/Canada | 508 recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| Class I, Zone 2, AEx nA IIC T4 | |
| Class I, Zone 2, Ex nA IIC T4 Gc X |
Power supply
| Nominal supply voltage | 24 V AC/DC ±20 % |
|---|---|
| Supply voltage range | 19.2 V AC/DC ... 28.8 V AC/DC |
| Typical current consumption | 40 mA (24 V DC) |
| Protective circuit | Surge protection Suppressor diode |
Serial interface
| Interface 1 | V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN 66259-1 |
|---|---|
| Connection method | D-SUB 9 plug |
| Transmission length | 15 m (shielded twisted pair) |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 13 |
| Pin assignment | DTE/DCE switchover via switch |
| Protocols supported | transparent protocol |
| Serial transmission speed | 115.2 kbps |
| Interface 2 | V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN 66259-1 |
| Connection method | Pluggable screw connection |
| Transmission length | 15 m (shielded twisted pair) |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 13 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 61000-6-3 |
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV (Test Level 3) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | Test Level 3 |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-5 |
| Signal | ± 2 kV (12 Ω) |
| Standards/regulations | EN 55011 |
| EN 61000-4-6 | |
| Conformance | CE-compliant |
| UL, USA/Canada | 508 recognized |
| Class I, Div. 2, Groups A, B, C, D | |
| Class I, Zone 2, AEx nA IIC T4 | |
| Class I, Zone 2, Ex nA IIC T4 Gc X | |
| DNV GL-Temperature | B |
| DNV GL-Humidity | A |
| DNV GL-Vibration | A |
| DNV GL-EMC | B |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| Shipbuilding approval | DNV GL |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |