The Phoenix Contact IBS IL 24 BK-T/U-2MBD-PAC Bus coupler serves as the head station for modular I/O islands, translating fieldbus communication into local peripheral bus signals. Bus couplers enable scalable expansion of sensors and actuators within centralized automation networks without rewiring individual control points. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for EtherNet/IP (EF007521): No
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- IO link master (EF007298): No
- System accessory (EF004118): Yes
- Degree of protection (IP) (EF005474): IP20
- With potential separation (EF003272): Yes
- Suitable for rail mounting (EF003972): Yes
- Wall mounting/direct mounting (EF007020): No
- Front built-in possible (EF007016): No
- Rack-assembly possible (EF007018): No
- Suitable for safety functions (EF001597): No
More info
▲Key Commercial Data
| Orderkey | 2862000 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 245 (AX-2009) |
| GTIN | 4017918974640 |
| Weight per Piece (excluding packing) | 142.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 142 g |
| Note on weight specifications | with connectors |
| Diagnostics messages | Peripheral fault yes, if the segment voltage USis not present |
Interfaces
| Designation | INTERBUS |
|---|---|
| No. of channels | 2 |
| Connection method | Inline shield connector |
| Transmission speed | 2 Mbps |
| Transmission physics | Copper |
| Designation | Remote bus branch / Inline local bus |
| Connection method | Inline data jumper |
| Transmission speed | 2 Mbps |
System limits of the bus coupler
| Number of local bus devices that can be connected | max. 63 |
|---|---|
| Number of devices with parameter channel | max. 62 |
| Number of supported branch terminals with remote bus branch | max. 15 |
Inline potentials
| Designation | Bus coupler supply UBC; Communications power UL(7.5 V) and the analog supply UANA(24 V) are generated from the bus coupler supply. |
|---|---|
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 100 mA (without connected Inline I/O terminals) |
| max. 1.25 A (with max. number of connected I/O terminal blocks) | |
| Designation | Communications power (UL) |
| Supply voltage | 7.5 V DC ±5 % |
| Power supply unit | max. 2 A DC (observe derating) |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 0.5 A DC (observe derating) |
| Designation | Main circuit supply (UM) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 8 A DC (sum of UM+ US) |
| Designation | Segment circuit supply (US) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 8 A DC (sum of UM+ US) |
Electrical isolation
| Test section | 5 V supply, incoming remote bus/5 V supply outgoing remote bus 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply incoming remote bus/7.5 V communications power, 24 V analog supply, 24 V bus coupler supply 500 V AC 50 Hz 1 min. | |
| 5 V supply, incoming remote bus/24 V main supply, 24 V segment supply 500 V AC 50 Hz 1 min. | |
| 5 V supply incoming remote bus / functional earth ground 500 V AC 50 Hz 1 min. | |
| 5 V supply, outgoing remote bus/24 V main supply, 24 V segment supply 500 V AC 50 Hz 1 min. | |
| 5 V supply outgoing remote bus/7.5 V communications power, 24 V analog supply, 24 V bus coupler supply 500 V AC 50 Hz 1 min. | |
| 5 V supply outgoing remote bus / functional earth ground 500 V AC 50 Hz 1 min. | |
| 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply/functional earth ground 500 V AC 50 Hz 1 min. | |
| 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply / 24 V main supply, 24 V segment supply 500 V AC 50 Hz 1 min. | |
| 24 V main supply, 24 V segment supply/functional earth ground 500 V AC 50 Hz 1 min. |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |