An Installation remote bus cable from Phoenix Contact, referenced as IBS INBC METER/E (2723152), is engineered to link modular I/O stations and controller architectures across distributed industrial automation networks. Bus cables provide robust data communication pathways that resist common factory floor electrical disturbances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Diameter conductor (EF001621): 1 mm
- Nominal cross section conductor (EF000060): 0.22 mm²
- Conductor category (EF001632): Class 2 = stranded
- Number of cores (EF001792): 9
- Specification core insulation (EF011805): Polyethylene (PE)
- Screen over stranding element (EF001623): Braiding
- Longitudinal water blocking cable (EF011011): No
- Radial water blocking cable (EF011012): No
- Suitable for underground installation (EF003689): No
- Material outer sheath (EF001625): Polyvinyl chloride (PVC)
- Low smoke according to EN IEC 61034-2 (EF003799): No
- Oil resistant according to EN IEC 60811-404 (EF009770): No
- Outer diameter approx. (EF003921): 9.7 mm
More info
▲Key Commercial Data
| Orderkey | 2723152 |
|---|---|
| Packing unit | 1 M |
| Note | Made to Order (non-returnable) |
| GTIN | 4017918141288 |
| Weight per Piece (excluding packing) | 137.600 g |
| Custom tariff number | 85444993 |
| Country of origin | DE (Germany) |
Cable
| Signal type/category | INTERBUS |
|---|---|
| Cable structure | 3 x 2 x 0.22 mm² + 3 x 1 mm² |
| Conductor cross section | 3x 2x 0.22 mm² (Data) |
| 3x 1 mm² (Supply) | |
| Conductor structure signal line | 7x 0.20 mm |
| Conductor structure, voltage supply | 14x 0.30 mm |
| Core diameter including insulation | 1 mm (Data) |
| 1.7 mm (Supply) | |
| Wire colors | green-yellow, white-brown, gray-pink, red, blue, green/yellow |
| Twisted pairs | 2 cores to the pair |
| Overall twist | 3 pairs and 3 wires to form the core |
| Shielding | Tinned copper braided shield |
| External sheath, color | black RAL 9005 |
| Inner sheath thickness | 0.9 mm |
| External cable diameter D | 9.7 mm ±0,3 mm |
| Minimum bending radius, fixed installation | 7.5 x D |
| Minimum bending radius, flexible installation | 15 x D |
| Outer sheath, material | PVC |
| Material, inner sheath | PVC |
| Material conductor insulation | PE |
| Conductor material | Bare Cu litz wires |
| Insulation resistance | ≥ 5 GΩ*km (Data) |
| ≥ 5 GΩ*km (Supply) | |
| Loop resistance | ≤ 186.00 Ω/km (Data) |
| ≤ 19.50 Ω/km (Supply) | |
| Cable capacity | ≤ 60 nF/km (At 800 Hz) |
| Wave impedance | 110 Ω ±20 Ω (at 64 kHz) |
| 95 Ω ±15 Ω (at >1 MHz) | |
| Near end crosstalk attenuation (NEXT) | ≥ 61 dB (at 772 kHz) |
| ≥ 59 dB (with 1 MHz) | |
| ≥ 55 dB (at 2 МHz) | |
| ≥ 50 dB (at 4 МHz) | |
| ≥ 46 dB (at 8 МHz) | |
| ≥ 44 dB (at 10 MHz) | |
| ≥ 41 dB (at 16 MHz) | |
| ≥ 40 dB (at 20 МHz) | |
| Attenuation | ≤ 10 dB/km (at 256 kHz) |
| ≤ 25 dB/km (at 772 kHz) | |
| ≤ 28 dB/km (with 1 MHz) | |
| ≤ 69 dB/km (at 4 МHz) | |
| ≤ 12 dB/km (at 10 MHz) | |
| ≤ 15.5 dB/km (at 16 MHz) | |
| ≤ 17.2 dB/km (at 20 МHz) | |
| Signal speed | 0.66 c |
| Coupling resistance | < 250.00 mΩ/m (at 30 MHz) |
| Nominal voltage, cable | 250 V (Peak value, not for high-power applications) |
| 450 V (Supply) | |
| Test voltage Core/Core | 1500 Vrms |
| Test voltage Core/Shield | 1000 Vrms |
| Flame resistance | according to VDE 0472, Part 804, test type B |
| according to IEC 60332-1 | |
| Ambient temperature (operation) | -30 °C ... 70 °C (cable, fixed installation) |
| -5 °C ... 70 °C (cable, flexible installation) |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |