Inline ME terminal Inline, Digital input module, Digital inputs: 4, 24 VDC, connection technology: 3 conductors, transmission speed on the local bus:500 kBit/s, protection index: IP20, including Inline connector and marking surface Inline, Digital input terminal, Digital inputs: 4, 24 V DC, connection technology: 3-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field

Automation > Fieldbus, decentr. periphery - digital I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact Inline ME terminal part IB IL 24 DI 4-ME is a modular I/O slice designed to mount onto standard DIN rail bus assemblies within control cabinets. It processes incoming control signals from industrial sensors, routing the digital telemetry back to the central processing unit via a local backplane bus.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Width: 12.2 mm
  • Height: 119.8 mm
  • Depth: 71.5 mm
  • Note on application Note on application: Only for industrial use
  • Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China.
  • Inline local bus Number of interfaces: 2
  • Connection method: Inline data jumper
  • Transmission speed: 500 kbps
  • Transmission physics: Copper
  • Module ID code (dec.): 190
  • ID code (hex): BE
  • Length code (hex): 41
  • Length code (dec): 65
  • Process data channel: 0 bit
  • Input address area: 4 bit
  • Output address area: 0 bit

More info

▲
Technical data

Dimensions
Dimensional drawing
Width12.2 mm
Height119.8 mm
Depth71.5 mm

Notes
Note on application
Note on applicationOnly for industrial use
Utilization restriction
CCCex noteUse in potentially explosive areas is not permitted in China.

Interfaces
Inline local bus
Number of interfaces2
Connection methodInline data jumper
Transmission speed500 kbps
Transmission physicsCopper

System properties
Module
ID code (dec.)190
ID code (hex)BE
Length code (hex)41
Length code (dec)65
Process data channel0 bit
Input address area4 bit
Output address area0 bit
Register length4 bit
Required parameter data1 Byte
Required configuration data4 Byte

Input data
Digital:
Input nameDigital inputs
Description of the inputEN 61131-2 type 1
Number of inputs4
Connection methodSpring-cage connection
Connection technology3-conductor
Input voltage24 V DC
Input voltage range-30 V DC ... 30 V DC
Input voltage range "0" signal-3 V DC ... 5 V
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input voltage UIN24 V DC
Nominal input current at UINmin. 3 mA (at nominal voltage)
Sensor current per channelmax. 250 mA
Typical response time< 1 ms

Product properties
Product typeI/O component
Product familyInline
Typemodular
Scope of deliveryincluding Inline connector and labeling field
No. of channels4
Operating modeProcess data operation with 4 bits
Data management status
Article revision09

Electrical properties
Maximum power dissipation for nominal condition0.6 W
Potentials: Communications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current drawmax. 40 mA
Potentials: Segment circuit supply (US)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 1 A
0 A
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic)/functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.

Connection data
Connection technology
Connection nameInline connector
Conductor connection
Connection methodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm
Inline connector
Connection methodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-25 °C ... 55 °C
Degree of protectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)

Standards and regulations
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting
Mounting typeDIN rail mounting