View larger
IB IL 24 DI 32/HD-2MBD-PAC 2692885 PHOENIX CONTACT Inline terminal
IB IL 24 DI 32/HD-2MBD-PAC
2692885
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - digital I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
IB IL 24 DI 32/HD-2MBD-PAC 2692885 PHOENIX CONTACT Inline terminal provides high-density digital input channels for monitoring numerous sensor inputs in compact control cabinet layouts. Such terminals optimize space while maintaining dependable signal acquisition for complex machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2692885
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 271 (AX-2009)
- GTIN: 4046356437455
- Weight per Piece (excluding packing): 211.300 g
- Custom tariff number: 85389091
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Width: 48.8 mm
- Height: 119.8 mm
- Depth: 71.5 mm
- Note on dimensions: Housing dimensions
- Ambient temperature (operation): -25 °C ... 55 °C
- Ambient temperature (storage/transport): -25 °C ... 85 °C
- Permissible humidity (operation): 10 % ... 95 % (according to DIN EN 61131-2)
More info
▲Key Commercial Data
| Orderkey | 2692885 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 271 (AX-2009) |
| GTIN | 4046356437455 |
| Weight per Piece (excluding packing) | 211.300 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 48.8 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 211.3 g |
| Note on weight specifications | with connectors |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | No |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 2 Mbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | max. 90 mA |
| Power consumption | max. 0.675 W |
| Designation | Segment circuit supply (US) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | max. 50 mA |
| Power consumption | max. 2.16 W (Module, complete) |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | EN 61131-2 type 1 |
| Connection method | Spring-cage connection |
| Connection technology | 1-wire |
| Number of inputs | 32 |
| Typical response time | 2 ms |
| Type of protection | Short-circuit and overload protection |
| Input voltage | 24 V DC |
| Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Nominal input current at UIN | typ. 2.8 mA |
| Typical input current per channel | 2.8 mA |
| Delay at signal change from 0 to 1 | 2 ms |
| Delay at signal change from 1 to 0 | 4 ms |
Electrical isolation
| Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. | |
| 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |