View larger
IB IL 24 DI 16-PAC 2861250 PHOENIX CONTACT Inline terminal
IB IL 24 DI 16-PAC
2861250
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - digital I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Inline terminal provides modular signal acquisition and distribution within industrial control cabinets, linking local field sensors directly to automation backplanes. These terminal blocks maintain clean electrical separation and reliable bus communication across complex manufacturing machinery.
Specific pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 16
- Number of digital outputs (EF001993): 0
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Input current at signal 1 (EF001428): 0.003 mA
- Permitted voltage at input (EF007554): -3 V
- Type of voltage (input voltage) (EF003033): DC
- Short-circuit protection, outputs available (EF003203): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces parallel (EF003026): 0
More info
▲Key Commercial Data
| Orderkey | 2861250 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 147 (C-6-2017) |
| GTIN | 4017918894191 |
| Weight per Piece (excluding packing) | 210.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Dimensions
| Dimensional drawing | |
|---|---|
| Width | 48.8 mm |
| Height | 140.5 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| 80 kPa ... 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) | |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 210 g |
| Note on weight specifications | with connectors |
| Operating mode | Process data mode with one word |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | max. 60 mA |
| Power consumption | max. 0.45 W |
| Designation | Segment circuit supply (US) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | max. 4 A |
| 0 A |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | EN 61131-2 type 1 |
| Connection method | Spring-cage connection |
| Connection technology | 3-wire |
| Number of inputs | 16 |
| Typical response time | < 1 ms |
| Input voltage | 24 V DC |
| Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Nominal input current at UIN | min. 3 mA (at nominal voltage) |
| Delay at signal change from 0 to 1 | 1 ms |
| Delay at signal change from 1 to 0 | 1 ms |
Electrical isolation
| Test section | 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. | |
| 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |