PHOENIX CONTACT DEK-OE-230AC/ 48DC/100 DEK-OE-230AC/ 48DC/100 2940210 PHOENIX CONTACT Solid-state relay terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DEK-OE-230AC/ 48DC/100 2940210 PHOENIX CONTACT Solid-state relay terminal block

DEK-OE-230AC/ 48DC/100

2940210

PHOENIX CONTACT

1 Pcs.

Solid-state relay terminal block Input solid-state relay terminal, input: 230 V AC, output: 3 - 48 V DC/ 100 mA, terminal width 6.2 mm

Automation > Optocoupler
Industrial Relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact model DEK-OE-230AC/ 48DC/100 is a solid-state relay terminal block designed for space-saving signal conditioning within control cabinets. Terminal block relays provide safe galvanic isolation between high-voltage control lines and low-voltage electronic inputs across complex industrial machinery.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Order information:: The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949).
  • Product type: Solid-state relay module
  • Product family: DEK
  • Application: Output function
  • Operating mode: 100% operating factor
  • Data management status Date of last data management: 03.05.2024
  • Article revision: 22
  • Insulation characteristics: Standards/regulations Insulation: Basic insulation
  • Overvoltage category: III
  • Pollution degree: 2
  • Test voltage (Input/output): 2.5 kV AC (Input/output)
  • Nominal input voltage U N: 230 V AC
  • Input voltage range in reference to U N: 0.9 ... 1.1
  • Input voltage range: 207 V AC ... 253 V AC
  • Switching threshold "0" signal, voltage: ≤ 92 V
  • Switching threshold "0" signal in reference to U N: ≤ 0.4

More info

▲
Technical data

Notes
Order information:The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949).
Note on applicationUse of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place.

Product properties
Product typeSolid-state relay module
Product familyDEK
ApplicationOutput function
Operating mode100% operating factor
Data management status
Date of last data management03.05.2024
Article revision22
Insulation characteristics: Standards/regulations
InsulationBasic insulation
Overvoltage categoryIII
Pollution degree2

Electrical properties
Test voltage (Input/output)2.5 kV AC (Input/output)

Input data
Nominal input voltage UN230 V AC
Input voltage range in reference to UN0.9 ... 1.1
Input voltage range207 V AC ... 253 V AC
Switching threshold "0" signal, voltage≤ 92 V
Switching threshold "0" signal in reference to UN≤ 0.4
Switching threshold "1" signal voltage≥ 207 V
Switching threshold "1" signal in reference to UN≥ 0.9
Typical input current at UN2.5 mA
Typical response time10 ms
Typical turn-off time20 ms
Operating voltage displayYellow LED
Protective circuitReverse polarity protection
Surge protection
Transmission frequency3 Hz

Output data
Contact switching type1 N/O contact
Design of digital outputelectronic
Output voltage range3 V DC ... 48 V DC
Limiting continuous current100 mA
Voltage drop at max. limiting continuous current≤ 0.9 V
Output circuit2-conductor floating, 3-conductor ground-referenced
Protective circuitReverse polarity protection; Polarity protection diode
Freewheeling diode; Freewheeling diode
Output resistorapprox. 22 kΩ (for 3-conductor operation)

Connection data
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm

Dimensions
Width6.2 mm
Height80 mm
Depth56 mm

Material specifications
Colorgreen (RAL 6021)

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-20 °C ... 60 °C
Ambient temperature (storage/transport)-20 °C ... 70 °C

Standards and regulations
Standards/regulations
Standards/regulationsIEC 60947-5-1

Mounting
Mounting typeDIN rail mounting
Assembly notein rows with zero spacing
Mounting positionany

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.