Phoenix Contact IB IL 24 PWR IN/2-F-PAC is an Inline terminal engineered for feeding and fusing system voltages within modular automation stations. Terminal units of this type ensure proper power management and bus segmentation across distributed industrial input/output nodes. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Width: 12.2 mm
- Height: 119.8 mm
- Depth: 71.5 mm
- Note on application Note on application: Only for industrial use
- Inline local bus Number of interfaces: 2
- Connection method: Inline data jumper
- Transmission speed: 500 kbps / 2 Mbps
- Register length: 0 bit
- Required parameter data: 0 Byte
- Required configuration data: 0 Byte
- Product type: I/O component
- Product family: Inline
- Type: modular
- Number of plugs: 1
- Special properties: 24 V DC
- Data management status Article revision: 05
More info
▲| Dimensional drawing | |
| Width | 12.2 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
| Note on application | |
| Note on application | Only for industrial use |
| Inline local bus | |
| Number of interfaces | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps / 2 Mbps |
| Module | |
| ID code (dec.) | none |
| ID code (hex) | none |
| Register length | 0 bit |
| Required parameter data | 0 Byte |
| Required configuration data | 0 Byte |
| Product type | I/O component |
| Product family | Inline |
| Type | modular |
| Number of plugs | 1 |
| Special properties | 24 V DC |
| UM, US | |
| With fuse (UM, US) | |
| Data management status | |
| Article revision | 05 |
| Insulation characteristics | |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
| 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. | |
| 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min. | |
| Protective circuit | Polarity protection, surge protection |
| Fuse | SI 5 x 20 6, 300 AT (in scope of delivery) |
| Supply | |
| Communications power UL | 7.5 V DC |
| I/O voltage | 24 V DC |
| I/O voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Residual ripple | ± ±5 % |
| Max. current consumption | 6 A (8 A) |
| Potentials: Main circuit supply (UM) | |
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V ... 30 V (including all tolerances, including ripple) |
| Potentials: Segment circuit supply (US) | |
| Supply voltage | 24 V DC (via Inline connector) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Connection technology | |
| Connection name | Inline connector |
| Conductor connection | |
| Connection method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Inline connector | |
| Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Mounting type | DIN rail mounting |