IB IL 120 DI 1-PAC 2861917 PHOENIX CONTACT Inline terminal is an input module designed for modular automation stations to capture discrete field signals and transmit them reliably to the controller. These terminals are commonly integrated into control cabinets to monitor sensor states in complex manufacturing processes. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2861917
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 150 (C-6-2017)
- GTIN: 4017918907464
- Weight per Piece (excluding packing): 39.000 g
- Custom tariff number: 85389091
- Country of origin: DE (Germany)
- Utilization restriction: 1
- Width: 12.2 mm
- Height: 119.8 mm
- Depth: 71.5 mm
- Ambient temperature (operation): -25 °C ... 55 °C
- Ambient temperature (storage/transport): -25 °C ... 85 °C
- Permissible humidity (storage/transport): 75 % ... 85 % (slight temporary condensation may sometimes appear on the housing)
- Air pressure (operation): 80 kPa ... 160 kPa (up to 2000 m above sea level)
More info
▲Key Commercial Data
| Orderkey | 2861917 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 150 (C-6-2017) |
| GTIN | 4017918907464 |
| Weight per Piece (excluding packing) | 39.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.) |
| Permissible humidity (storage/transport) | 75 % ... 85 % (slight temporary condensation may sometimes appear on the housing) |
| Air pressure (operation) | 80 kPa ... 160 kPa (up to 2000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | max. 30 mA |
| Designation | I/O supply |
| Supply voltage | 120 V AC (via voltage jumper) |
| Current consumption | 0.25 A |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | IEC 61131-2 type 1 |
| Connection method | Spring-cage connection |
| Connection technology | 3-wire |
| Number of inputs | 1 |
| Input voltage | 120 V AC |
| Input voltage range "0" signal | 0 V AC ... 40 V AC |
| Input voltage range "1" signal | 77 V AC ... 135 V AC |
Electrical isolation
| Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. | |
| 7.5 V supply (bus logics) / I/O area 2500 V AC 50 Hz 1 min. | |
| Routine test 1200 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | I, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |